2015-12-02 13:09:514920 LORING DRIVE
 PERMIT #15110832
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
 MATERIAL DATA SHEETS SHALL BE PROVIDED TO THE ON-SITE
 INSPECTOR TO INDICATE CORRECT TORQUE WRENCH SETTINGS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE
 INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS
 OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER,
 AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS.
  
 PROVIDE CHAIN WITH LOCK FOR SUPERVISING THE BACKFLOW
 PREVENTER IN THE OPEN POSITION.
  
 FIRE DEPARTMENT CONNECTIONS SHALL BE VISIBLE AND
 RECOGNIZABLE FROM THE STREET OR NEAREST POINT OF FIRE
 DEPARTMENT APPARATUS ACCESSIBILITY OR ON THE STREET
 SIDE OF BUILDINGS. CONNECTIONS SHALL BE LOCATED NOT
 MORE THAN 100 FEET FROM THE NEAREST FIRE HYDRANT
 CONNECTED TO AN APPROVED WATER SUPPLY.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  