Plan Review Notes For Permit 15110823 |
Permit Number |
15110823 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-03-18 11:32:39 | 3RD ELECTRICAL REVIEW NOTES FOR REVISION #:15110823 | | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 | | NFPA 70 2011 (NEC) | | | | CORRECTIONS REQUIRED: | | SHEET E213 | | 1. THE MANDATORY LIGHT CONTROL REQUIRED BY FBC-E | | SECTION 405 IS NOT DEFINED. THIS ALSO APPLIES TO | | COMMENT #4 WHICH ADDRESSES ENERGY MANAGEMENT AS WELL. | | 2. THE WP GFI OUTLET SHOWN DOES NOT COMPLY WITH | | NEC406.9(B). NOTE MADE ON E008 AS WELL. PER NEC | | REQUIREMENTS, IN ADDITION TO THE IN-USE TYPE COVERS AND | | CAST BOXES, EVERY RECEPTACLE IN A WET LOCATION SHALL BE | | LISTED WEATHER RESISTANT. ADD NOTE TO SHEET E000 SYMBOL | | LEGEND AS WELL. | | SHEET E603 | | 1. RENAME CKT 5 TO MATCH RISER DIAGRAM ON E001 | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|