2016-02-25 14:40:29 | 2ND ELECTRICAL REVIEW NOTES FOR REVISION #:15110823 |
| REVIEWED FOR COMPLIANCE WITH: |
| FBC 2010 EDITION |
| NFPA 70 2008 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| SHEET E001 & E002 |
| 1. DEFINE ON THIS RISER DIAGRAM THE AREA OR AREAS |
| AFFECTED BY THIS PROJECT. |
| SHEET E008 |
| 1. YOU SUBMITTED A FIXTURE SCHEDULE THAT IS PROBABLY |
| FOR THE MASTER PERMIT BUT HAVE NOT SUBMITTED ANY |
| LIGHTING PLANS OR DESIGN FOR THIS SCOPE OF WORK. |
| SHEET E201 & E213 |
| 1. MISSING GROUNDING DETAIL 11 ON SHEET E701. |
| 2. MISSING TRANSFORMER SUPPORT DETAIL 3 ON SHEET E701. |
| 3. DEFINE THE AREA OF WORK ON THE FLOOR PLANS. |
| 4. YOU NEED TO SUBMIT A CODE COMPLIANT LIGHTING DESIGN |
| FOR THE AREA IN QUESTION. THIS SHALL TAKE INTO |
| CONSIDERATION ALL THE REQUIREMENTS OF THE FBC-ENERGY |
| CONSERVATION. |
| 5. YOU SHALL INCLUDE THE REQUIRED EMERGENCY AND EXIT |
| LIGHTS FOR THE WORK AREA. |
| SHEET E602 & E603 |
| 1. ONCE THE SCOPE OF WORK OR AREA OF WORK IS DEFINED |
| AND THE LIGHTING PLAN PROVIDED THE PANEL AND CIRCUIT |
| DESIGNATIONS CAN BE REVIEWED. |
| SHEET G000 |
| 1. CORRECT THE DRAWING SCHEDULE TO INCLUDE ALL OF AND |
| ONLY THOSE SHEETS PERTINENT TO THIS PROJECT. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |