2015-12-19 07:40:501) THERE ARE PLANS IN THIS PERMIT FOR THE GENERATOR.
 THIS PERMIT IS FOR THE COOLING TOWER. CLARIFY.
 2) THE WATER SUPPLY CONNECTION TO THE TOWER SHALL BE
 EQUIPPED WITH A LEAD FREE REDUCED PRESSURE BACKFLOW
 PREVENTER. SHOW THE SIZE AND LOCATION OF THE BACKFLOW
 PREVENTER ON THE PLANS. SUBMIT MANUF. SPECS ON THE BFP
 DEVICE. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 UTILITIES DEPT. CENTRAL OPERATIONS AT 561-822-2210 FOR
 ADDITIONAL INFORMATION ON THE BACKFLOW PREVENTION
 DEVICE REQUIREMENTS.
  