2015-12-16 14:45:081ST REVIEW 2014 MECHANICAL
 PERMIT 15110823
 12/16/15
  
 1) PLEASE ADJUST THE VALUE ON THE PERMIT APPLICATION TO
 INCLUDE THE COST OF THE PROJECT BASED ON LABOR,
 MATERIALS, EQUIPMENT, DESIGN FEES, OVERHEAD AND PROFIT
 ETC.- REFER TO SECTION 109.3 WPB AMENDMENTS TO THE
 FBC-14.
 2) SHEET S1.4: PROVIDE STRUCTURAL DETAILS FOR
 CONSTRUCTION OF THE COOLING TOWER STEEL SUPPORT BASE,
 AND ATTACHMENT OF TOWER TO THE SUPPORT BEAMS- SECTION
 301.15 FBC-14 MECHANICAL.
 3 )M1.0: PROVIDE ENGINEERED DETAILS FOR SUPPORT AND
 TIE-DOWN OF THE ABOVE GROUND CHILLER WATER SUPPLY AND
 RETURN PIPINGS.
 4) M1.0: INDICATE THE TYPE, THICKNESS, AND R-VALUE OF
 THE ABOVEGROUND CHILLED WATER PIPING INSULATION.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOLING
 TOWER REVIEWED AND APPROVED BY THE ENGINEER OF RECORD
  