Plan Review Notes
Plan Review Notes For Permit 15110808
Permit Number 15110808
Review Stop M
Sequence Number 1
Notes
Date Text
2015-11-24 11:59:161ST REVIEW 2014 MECHANICAL
 PERMIT #15110808
 11/24/15
  
 1) IN REFERENCE TO THE VEHICLE DELIVERY GARAGE PLEASE
 SEE SECTION 404.1 ENCLOSED PARKING GARAGES.
 MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED PARKING
 GARAGES SHALL BE PERMITTED TO OPERATE INTERMITTENTLY IN
 ACCORDANCE WITH ITEM 1, ITEM 2 OR BOTH.
 1. THE SYSTEM SHALL BE ARRANGED TO OPERATE
 AUTOMATICALLY UPON DETECTION OF VEHICLE OPERATION OR
 THE PRESENCE OF OCCUPANTS BY APPROVED AUTOMATIC
 DETECTION DEVICES.
 2. THE SYSTEM SHALL BE ARRANGED TO OPERATE
 AUTOMATICALLY BY MEANS OF CARBON MONOXIDE DETECTORS
 APPLIED IN CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS.
 SUCH DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH
 THEIR MANUFACTURER'S RECOMMENDATIONS.
 A) SHEET M1.1: BASED ON THE CODE SECTION ABOVE,
 NITROGEN DIOXIDE DETECTORS SHALL BE INSTALLED ALONG
 WITH THE CO DETECTORS. REVISE THE PLANS ACCORDINGLY AND
 SUBMIT CUT SHEETS FOR THE DETECTORS REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
 B) EXHAUST VENTILATION AT A RATE OF .75 CFM/SF. SHALL
 BE INSTALLED IN THE VEHICLE DELIVERY GARAGE- TABLE
 403.3. REVISE THE PLANS TO SHOW THE LCATIONS OF THE
 EXHAUST FAN(S) AND PROVIDE A SEQUENCE OF OPERATION.
 PROVIDE AN EQUIPMENT SCHEDULE FOR THE FANS AND SUBMIT
 PRODUCT SPECS.
 C) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 NEW EXHAUST FAN(S) AT THE SERVICE/RECEPTION AREAS, AND
 SUBMIT MANUFACTUTERS'S CUT SHEETS AND MIAMI DADE NOA'S
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD.
 3) SHEET M0.1 & M1.1: DUCT SMOKE DETECTORS ARE LISTED
 AS NOT REQUIRED IN THE SCHEDULE, HOWEVER, IN ACCORDANCE
 WITH SECTION 606.2.1 DETECTORS ARE REQUIRED TO BE
 PLACED IN THE RETURN AIR PLENUMS OF RTU'S 1, 3, 6, & 9.
 PLEASE PROVIDE AN INSTALLATION DETAIL AND EQUIPMENT
 SCHEDULE ON THE PLAN, AND SUBMIT MANUFACTURER 'S
 SPECIFICATIONS REVIEW AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD,
 4) M0.1 THE DESIGN CRITERIA FOR THE AC SYSTEM LISTS
 INCORRECT WET AND DRY BULB TEMPERATURES. SEE APPENDIX D
 FBC-14 PLUMBING, AS SHOWN IN THE TABLE THE DRY BULB
 TEMP FOR WPB IS 91 DEGREES, AND THE WET BULB IS 79
 DEGREES: PLEASE CORRECT THE PLAN.
 5) M1.1: BALANCED RETURN AIR IS REQUIRED FOR AHU-1,
 HOWEVER THE PLAN DOESN'T SHOW HOW AIR BEING SUPPLIED
 INTO THE GEN. MANAGER'S OFFICE AND THE MIDDLE CONSULT
 ROOM IS BEING RETURNED TO THE UNIT- SEE SECTION 601.5
 FBC-14 MECHANICAL.
 6) PROVIDE SITE SPECIFIC WIND LOAD TIE DOWN ENGINEERING
 FOR THE NEW ROOF TOP EXHAUST FANS- SECTION 301.15,, AND
 SUBMIT NOA'S OR FL. PRODUCT APPROVALS FOR THE EQUIPMENT
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  