2015-11-30 16:02:35 | PERMIT #15110808 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| FAILED COMMENTS: |
| |
| 1) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| |
| 3) NOTES INDICATE THET BUILDING IS FULL SPRINKLERED, |
| HOWEVER THERE ARE NO DRAWINGS FOR WORK BEING DONE TO |
| SPRINKLER SYSTEM. ENGINEERED FIRE ALARM AND FIRE |
| SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A |
| GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS |
| BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| DOCUMENTS) FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS |
| ARE REQUIRED FOR THE INSTALLATION OR MODIFICATION OF |
| THE FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM. |
| |
| 4) SEE MECHANICAL PLAN REVIEWER COMMENTS. IF SMOKE |
| DETECTORS ARE INSTALLED OR WILL BE INSTALLED, PER LOCAL |
| AHJ POLICY, DUCT SMOKE DETECTORS SHALL INITIATE A |
| GENERAL FIRE ALARM CONDITION. |
| |
| |
| SUE ELLEN CALDERON |
| ASST. FIRE MARSHAL |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 644-7326 |
| |
| |