2016-02-25 17:07:392ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110794
 2/25/16
  
 1) DERM APPROVAL ACCEPTABLE TO BE SUBMITTED PRIOR TO
 1ST INSPECTION.
 2) COMMENT #6 FROM THE 1ST REVIEW STILL EXISTS. THE
 EXHAUST DUCT PENETRATING THE COMBUSTIBLE ROOF SURFACE
 SHOWN ON SHEET M101 MUST BE GUARDED IN ACCORDANCE WITH
 SECTION 8.3.3 NFPA-37- PROVIDE A METAL VENTILATED
 THIMBLE NOT LESS THAN 12" IN DIAMETER THAN THE EXHAUST
 PIPE OR A METAL OR BURNED FIRE CLAY THIMBLE CONSTRUCTED
 OF BRICKWORK OR OTHER FIREPROOFING MATERIALS PROVIDING
 NOT LESS THAN 8" OF INSULATION BETWEEN THE THIMBLE AND
 THE COMBUSTIBLE ROOF PLYWOOD.
 3) SHEET M503: THE TWO DETAILS FOR THE ROOF FAN AND THE
 DUCT PENETRATION APPEAR TO INDICATE A FLAT ROOF
 SURFACE, HOWEVER THE PLAN IS INDICATING A SLOPED ROOF
 SURFACE. PLEASE PROVIDE COMPLETE MOUNTING DETAILS FOR
 SLOPED ROOF INSTALLATIONS INDICATING HOW THE FAN AND
 DUCT WILL BE ATTACHED TO THE CURBS, AND HOW THE CURBS
 WILL BE ATTACHED TO THE ROOF. SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND A CURRENT PRODUCT APPROVAL/AND OR
 MIAMI-DADE NOA FOR THE ROOF FAN REVIEWED AND APPROVED
 BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  