Plan Review Notes
Plan Review Notes For Permit 15110794
Permit Number 15110794
Review Stop M
Sequence Number 1
Notes
Date Text
2015-12-16 10:24:481ST REVIEW 2014 MECHANICAL
 PERMIT #15110794
 12/16/15
  
 1) ADVIORY: UNDERGROUND FUEL TANKS AND DELIVERY SYSTEMS
 EXCEEDING 550 GALLONS MUST BE APPROVED BY THE PALM
 BEACH COUNTY DEPARTMENT OF ENVIRONEMNETAL RESOURCE
 MANAGEMENT. PROVIDE DOCUMENTATION OF APPROVAL FOR THE
 8000 GALLON DIESEL FUEL TANK INSTALLATION.
 2) PROVIDE A SOIL REPORT FROM A FL. LICENSED ENGINEER
 FOR INSTALLATION OF THE UNDERGROUND TANK AND NEW
 GENERATOR BUILDING- SEE SECTION 1803 FBC-14 BUILDING.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, FUEL TANK, FUEL PIPING, AND THE GENERATOR
 EXHAUST FAN APPROVED BY THE ENGINEER OF RECORD.
 4) PROVIDE ON THE PLANS THE WIND LOAD DESIGN CRITERIA
 AS OUTLINED IN SECTION 1609 FBC-14 BUILDING.WIND DESIGN
 CRITERIA 2010 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10.
 SECTION 1609.3 BASIC WIND SPEED FIGURE 1609.A-C.
 SECTION 1609.3 WIND SPEED CONVERSION
 A) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 B) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 C) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 D) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 E) COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2).
 F) COMPONENTS AND CLADDING/ 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS FOR THE
 MECHANICAL SYSTEMS: THE INTAKE AND EXHAUST LOUVERS, AND
 ROOF MOUNTED EXHAUST FAN. PLEASE NOTE SITE SPECIFIC
 ENGINEERING IS REQUIRED FOR ATTACHMENT OF ALL EXTERIOR
 EQUIPMENT AND APPLIANCES- PROVIDE ATTACHMENT DETAILS.
 5) INDICATE WHICH CODE OR STANDARD WAS USED TO
 CALCULATE AND DESIGN THE EXHAUST SYSTEM FOR THE
 GENERATOR BUILDING AND SHOW THE VENTILATION
 CALCULATION.
 6) PROVIDE A SECTION VIEW OF THE EXHAUST DUCT FROM THE
 OUTLET OF THE GENERATOR TO THE TERMINATION CAP ON THE
 ROOF- INDICATE THE TYPE OF DUCT WORK AND HOW THE DUCT
 WILL BE GUARDED WHERE IT PENETRATES THE COMBUSTIBLE
 ROOF PLYWOOD- REFER TO SECTION 8.3.3 NFPA-37.
 7) PROVIDE A SEQUENCE OF OPERATION FOR THE
 THERMOSTATICALLY CONTROLLED EXHAUST FAN- SEE SHEET
 M101.
 8) REFER TO SECTION 501.3.1 ITEM #1 AND VERIFY
 COMPLIANCE FOR THE GENERATOR EXHAUST TERMINATION.
 9) PLEASE ADJUST THE VALUE ON THE PERMIT APPLICATION TO
 INCLUDE THE COST OF THE PROJECT BASED ON LABOR,
 MATERIALS, EQUIPMENT, DESIGN FEES, OVERHEAD AND PROFIT
 ETC.- REFER TO SECTION 109.3 WPB AMENDMENTS TO THE
 FBC-14.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  