2016-01-21 13:12:39 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1. GENERAL NOTES #12: THE WORDS ?ROMEX? & ?BX? AS USED |
| IN THIS NOTE IS TO IDENTIFY A TYPE OF CABLE. ROMEX IS A |
| BRAND NAME AND NOT A CABLE TYPE, REFER TO CABLE TYPES |
| ?NM?, ?NMC? OR ?NMS? AND CORRECT THE NOTE ACCORDINGLY. |
| 2. GENERAL NOTES #14 PROHIBIT THE USE OF FUSES. THE |
| DISCONNECT ON THE EXTERIOR SURFACE OF THE SHELTER SHALL |
| HAVE A PROPERLY RATED CIRCUIT BREAKER. |
| 3. CORRECT THE UTILITY SOURCE CONDUCTOR LABELING IN THE |
| METER DETAIL ON SHEET E4 FOR A REGULAR 120/240 SINGLE |
| PHASE SERVICE. |
| 4. PROVIDE LOAD CALCS FOR THE PROPOSED 800 AMP SERVICE. |
| 5. PROVIDE A CIRCUIT DIRECTORY. |
| 6. PROVIDE SHELTER DETAILS. IF THE SHELTER IS TO BE A |
| SELF-CONTAINED PREMANUFACTURERD UNIT, PROVIDE THE |
| ELECTRICAL SPEC SHEET WITH THE REQUIREMENTS. IF IT IS |
| TO BE SITE BUILT, SUBMIT A CODE COMPLIANT ELECTRICAL |
| FLOOR PLAN. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |