2016-02-16 12:49:01 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL | | REVIEW CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | NOTE: | | MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | MEANS CONTRACTOR WILL SUBMIT THE REQUESTED ITEMS AFTER | | THE PERMIT IS ISSUED. REVISION FEES MAY APPLY. | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS OK OR IF | | RE-SUBMITTING REQUESTED ITEMS BEFORE ISSUING THE | | PERMIT. | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS THAT | | ARE DONE WITH AN APPROVED HEATING AND COOLING | | CALCULATION METHOD AS REQUIRED BY SEC. R403.6.1 OF | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | INFORMATION SUBMITTED IS NOT AN APPROVED METHOD. | | (REPEAT COMMENT). | | | | 2- VERTICAL A/C UNIT DETAIL SHOWN ON SHEET M.1 DOESN'T | | MATCH PROPOSED INSTALLATION. SEC. 107.2.1 CITY | | AMENDMENTS. (REPEAT COMMENT). | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD | | DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD | | DRAWINGS FOR REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|