2015-12-28 14:27:58NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS THAT
 ARE DONE WITH AN APPROVED HEATING AND COOLING
 CALCULATION METHOD AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 INFORMATION SUBMITTED IS NOT AN APPROVED METHOD.
  
 2- A/C DRAWING TO HAVE THE EQUIPMENT MANUFACTURER'S
 NAME AND MODEL NUMBER SHOWING THE SENSIBLE AND AND
 TOTAL COOLING CAPACITY AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 3- A/C PLANS SHOWING ON SHEET M.1 DOESN'T COMPLY WITH
 THE BALANCED RETURN AIR SEC. M1602.4 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE COMPLETE
 INFORMATION FOR THE BALANCED RETURN AIR ON ALL
 BEDROOMS.
  
 4- PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE
 NUMBER OF CONNECTORS AS SPECIFIED ON THE CONDENSING
 UNIT MOUNTING DETAIL ARE ADEQUATE TO RESIST THE WIND
 LOADS OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). CHECK CONNECTIONS TO THE CONCRETE SLAB AND TO
 THE CONDENSING UNIT. ALSO, SPECIFY HOW LONG ARE THE
 3/8" BOLTS AND ANCHORS SPECIFIED.
  
 5- VERTICAL A/C UNIT DETAIL SHOWN ON SHEET M.1 DOESN'T
 MATCH PROPOSED INSTALLATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  