2015-12-28 14:27:58 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014) |
| |
| 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS THAT |
| ARE DONE WITH AN APPROVED HEATING AND COOLING |
| CALCULATION METHOD AS REQUIRED BY SEC. R403.6.1 OF |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| INFORMATION SUBMITTED IS NOT AN APPROVED METHOD. |
| |
| 2- A/C DRAWING TO HAVE THE EQUIPMENT MANUFACTURER'S |
| NAME AND MODEL NUMBER SHOWING THE SENSIBLE AND AND |
| TOTAL COOLING CAPACITY AS REQUIRED BY SEC. R403.6.1 OF |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| 3- A/C PLANS SHOWING ON SHEET M.1 DOESN'T COMPLY WITH |
| THE BALANCED RETURN AIR SEC. M1602.4 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE COMPLETE |
| INFORMATION FOR THE BALANCED RETURN AIR ON ALL |
| BEDROOMS. |
| |
| 4- PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE |
| NUMBER OF CONNECTORS AS SPECIFIED ON THE CONDENSING |
| UNIT MOUNTING DETAIL ARE ADEQUATE TO RESIST THE WIND |
| LOADS OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). CHECK CONNECTIONS TO THE CONCRETE SLAB AND TO |
| THE CONDENSING UNIT. ALSO, SPECIFY HOW LONG ARE THE |
| 3/8" BOLTS AND ANCHORS SPECIFIED. |
| |
| 5- VERTICAL A/C UNIT DETAIL SHOWN ON SHEET M.1 DOESN'T |
| MATCH PROPOSED INSTALLATION. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD |
| DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD |
| DRAWINGS FOR REFERENCE. |
| |