2016-01-04 11:46:05 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6700 | | [email protected] | | ALTERNATE CONTACT | | MIKE ALBARRAN | | 561-805-6746 | | [email protected] | | | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | FEET OF EACH SLEEPING ROOM. PLEASE SHOW ON FLOOR PLANS. | | R404.1 LIGHTING EQUIPMENT (MANDATORY). MUST BE IC RATED | | AND SEALED TYPE RECCESSED FIXTURES. | | A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY | | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY | | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY | | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH | | EFFICACY LAMPS. | | SHOW NEC 2011 ON STANDARDS INSTEAD OF 2008 . BOXES AT | | CEILING-SUSPENDED (PADDLE) FAN OUTLETS. | | OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE | | SUPPORT | | OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE LISTED, | | SHALL BE | | MARKED BY THEIR MANUFACTURER AS SUITABLE FOR THIS | | PURPOSE, | | AND SHALL NOT SUPPORT CEILING-SUSPENDED (PADDLE) FANS | | THAT | | WEIGH MORE THAN 32 KG (70 LB). FOR OUTLET BOXES OR | | OUTLET BOX | | SYSTEMS DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) | | FANS | | THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED | | MARKING SHALL | | INCLUDE THE MAXIMUM WEIGHT TO BE SUPPORTED. NEC 314.28 | | C |
|