Plan Review Notes
Plan Review Notes For Permit 15110777
Permit Number 15110777
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-04 11:46:051ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM. PLEASE SHOW ON FLOOR PLANS.
 R404.1 LIGHTING EQUIPMENT (MANDATORY). MUST BE IC RATED
 AND SEALED TYPE RECCESSED FIXTURES.
 A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS.
 SHOW NEC 2011 ON STANDARDS INSTEAD OF 2008 . BOXES AT
 CEILING-SUSPENDED (PADDLE) FAN OUTLETS.
 OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT
 OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE LISTED,
 SHALL BE
 MARKED BY THEIR MANUFACTURER AS SUITABLE FOR THIS
 PURPOSE,
 AND SHALL NOT SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT
 WEIGH MORE THAN 32 KG (70 LB). FOR OUTLET BOXES OR
 OUTLET BOX
 SYSTEMS DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE)
 FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL
 INCLUDE THE MAXIMUM WEIGHT TO BE SUPPORTED. NEC 314.28
 C