2015-12-23 14:05:01 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014) |
| |
| 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JG RD.) FOR |
| IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS |
| AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT |
| FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- PROVIDE SPECIFICATIONS FOR THE INTERIOR GARAGE DOOR |
| LEADING FROM THE GARAGE TO THE MAIN HOUSE TO SHOW |
| COMPLIANCE WITH SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| NOTE: DOOR NEEDS TO BE SELF-CLOSING ALSO. |
| |
| 3- SPECIFY SAFETY GLASS FOR WINDOW IN BEDROOM #2, |
| MASTER BEDROOM AND WINDOW ADJACENT TO THE DOOR IN THE |
| REAR DECK. SEC. R308.4.2 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| 4- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| R401.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| NOTE: WATER CAN NOT BE DIVERTED TO THE NEIGHBOR'S. |
| |
| 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE HANDRAILS AND GUARDRAILS SHOWING |
| COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| ALSO, OPENINGS TO COMPLY WITH SEC. R312.13 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE OPENING |
| SIZE SPECIFIED ON STAIR DETAIL #5 ON SHEET A3. THE CODE |
| REQUIRES A DIMENSION THAT DOESN'T ALLOW A 4" SPHERE TO |
| PAS THRU. 4" SPACING BETWEEN PICKETS WILL ALLOW A 4" |
| SPHERE TO PASS THRU. REVISE AS REQUIRED. |
| |
| 6- SPECIFY CARBON MONOXIDE ALARM WITHIN THE BEDROOMS AS |
| REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| |
| 7- PROVIDE 2 COPIES OF THE GEOTECHNICAL EXPLORATION |
| ENGINEERING REPORT. ONLY ONE WAS SUBMITTED. SEC. 107.1 |
| CITY AMENDMENTS. |
| |
| 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) HURRICANE SHUTTERS FOR DOORS AND WINDOWS THAT DON'T |
| HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE INSTALLATION SCHEDULE CITY SAMPLE. OR |
| PROVIDE COMPLETE INFORMATION ON ANY OTHER FORMAT THAT |
| CONTAINS ALL THE REQUIRED INFORMATION. |
| |
| B) ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS. |
| |
| C) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY |
| IDENTIFY MULLION SIZE TO VERIFY THE DESIGN PRESSURES. |
| |
| D) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| E) GABLE END VENT AS SPECIFIED ON WEST ELEVATION ON |
| SHEET A2. |
| |
| F) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED |
| ON PLANS AND ALL DETAILS. PROVIDE ONLY THE FLORIDA |
| PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT |
| APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| NOTE: SOME FLORIDA PRODUCT APPROVALS LISTED ON THE |
| CONNECTOR SCHEDULE ON SHEET S2 NEED TO BE UPDATED TO |
| THE 2014 FLORIDA PRODUCT APPROVAL CODE VERSION. |
| |
| G) METAL ROOFING AS SPECIFIED ON PLANS. |
| |
| H) EXTERIOR SWING DOOR BY THE REAR DECK AS SHOWN ON |
| PLANS. |
| |
| I) SLIDING GLASS DOOR AS SHOWN ON PLANS. |
| |
| 9- ARCHITECT OF RECORD TO APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 10- ENERGY CALCULATIONS SUBMITTED; |
| A) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING |
| BUILDER NAME, PERMIT OFFICE AND JURISDICTION #. SEC. |
| R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| B) OWNER OR AGENT NEED TO CERTIFY COMPLIANCE AT THE |
| BOTTOM OF THE FORM. SEC. R103.1.1.3 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| NOTE: WRITING THE NAME OF THE OWNER AT THE BOTTOM OF |
| THE FORM DOESN'T SATISFY THE REQUIREMENT.. OWNER OR |
| AGENT NEED TO PHYSICALLY CERTIFY COMPLIANCE AT THE |
| BOTTOM OF THE FORM. |
| |
| C) WALL TYPES ITEM #9 IS MISSING THE ADJACENT WALL |
| SEPARATING THE GARAGE FROM THE MAIN HOUSE. INSULATION |
| REQUIRED. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014). |
| |
| D) REVISE THE CLIMATE ZONE. SEE TABLE R301.1 OF |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| E) REVISE DOORS SPECIFIED ON PAGE 3 OF 5. NEED TO MATCH |
| PLANS AND PRODUCT APPROVALS SUBMITTED. SIZE SPECIFIED |
| FOR THE ENTRY DOOR DOESN'T MATCH PLANS. |
| NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED ON THE |
| GLAZING CALCULATIONS NO DOORS. SLIDING GLASS DOORS NEED |
| TO BE CONSIDERED IN WINDOWS SECTION. SEE SEC. |
| R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014) |
| |
| F) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO |
| MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014) |
| |
| G) TABLE 402.4.1.1 SUBMITTED IS INCOMPLETE. THERE ARE |
| ITEMS THAT NEED TO BE CHECKED. SEC. R103.2 OF |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014) |
| |
| H) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE |
| U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY |
| CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS |
| ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| |
| 11- CLEARLY SPECIFY ALL DESIGN LOADS INCLUDING THE |
| ATTIC LIVE LOADS AS REQUIRED BY FOOTNOTES "B" AND "G" |
| OF TABLE R301.5 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 12- THE ROOF PROJECTION ON THE SOUTH SIDE NEEDS TO |
| COMPLY WITH THE 1 HOUR ON THE UNDERSIDE FIRE RATING AS |
| REQUIRED BY TABLE R302.1. (1) OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). PROVIDE COMPLETE DETAIL AND |
| SPECIFICATIONS FOR THE ROOF PROJECTION ON THE SOUTH |
| SIDE. |
| NOTE: KEEP IN MIND THAT VENTS ON THE UNDERSIDE OF THE |
| ROOF PROJECTIONS DON'T COMPLY WITH THE 1 HR FIRE |
| RATING. |
| |
| 13- SHEET A1: ARCHITECT CALLS FOR WINDOWS AND DOORS |
| IMPACT GLASS FOR HURRICANE PROTECTION. PRODUCT |
| APPROVALS SUBMITTED ARE NOT IMPACT GLASS. PLANS AND |
| PRODUCT APPROVALS TO MATCH. REVISE AS REQUIRED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD |
| DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD |
| DRAWINGS FOR REFERENCE. |
| |