2015-12-23 14:05:01NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE SPECIFICATIONS FOR THE INTERIOR GARAGE DOOR
 LEADING FROM THE GARAGE TO THE MAIN HOUSE TO SHOW
 COMPLIANCE WITH SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 NOTE: DOOR NEEDS TO BE SELF-CLOSING ALSO.
  
 3- SPECIFY SAFETY GLASS FOR WINDOW IN BEDROOM #2,
 MASTER BEDROOM AND WINDOW ADJACENT TO THE DOOR IN THE
 REAR DECK. SEC. R308.4.2 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 NOTE: WATER CAN NOT BE DIVERTED TO THE NEIGHBOR'S.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE HANDRAILS AND GUARDRAILS SHOWING
 COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 ALSO, OPENINGS TO COMPLY WITH SEC. R312.13 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE OPENING
 SIZE SPECIFIED ON STAIR DETAIL #5 ON SHEET A3. THE CODE
 REQUIRES A DIMENSION THAT DOESN'T ALLOW A 4" SPHERE TO
 PAS THRU. 4" SPACING BETWEEN PICKETS WILL ALLOW A 4"
 SPHERE TO PASS THRU. REVISE AS REQUIRED.
  
 6- SPECIFY CARBON MONOXIDE ALARM WITHIN THE BEDROOMS AS
 REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 7- PROVIDE 2 COPIES OF THE GEOTECHNICAL EXPLORATION
 ENGINEERING REPORT. ONLY ONE WAS SUBMITTED. SEC. 107.1
 CITY AMENDMENTS.
  
 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HURRICANE SHUTTERS FOR DOORS AND WINDOWS THAT DON'T
 HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE INSTALLATION SCHEDULE CITY SAMPLE. OR
 PROVIDE COMPLETE INFORMATION ON ANY OTHER FORMAT THAT
 CONTAINS ALL THE REQUIRED INFORMATION.
  
 B) ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY THE DESIGN PRESSURES.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) GABLE END VENT AS SPECIFIED ON WEST ELEVATION ON
 SHEET A2.
  
 F) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND ALL DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
 NOTE: SOME FLORIDA PRODUCT APPROVALS LISTED ON THE
 CONNECTOR SCHEDULE ON SHEET S2 NEED TO BE UPDATED TO
 THE 2014 FLORIDA PRODUCT APPROVAL CODE VERSION.
  
 G) METAL ROOFING AS SPECIFIED ON PLANS.
  
 H) EXTERIOR SWING DOOR BY THE REAR DECK AS SHOWN ON
 PLANS.
  
 I) SLIDING GLASS DOOR AS SHOWN ON PLANS.
  
 9- ARCHITECT OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- ENERGY CALCULATIONS SUBMITTED;
 A) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER NAME, PERMIT OFFICE AND JURISDICTION #. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) OWNER OR AGENT NEED TO CERTIFY COMPLIANCE AT THE
 BOTTOM OF THE FORM. SEC. R103.1.1.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: WRITING THE NAME OF THE OWNER AT THE BOTTOM OF
 THE FORM DOESN'T SATISFY THE REQUIREMENT.. OWNER OR
 AGENT NEED TO PHYSICALLY CERTIFY COMPLIANCE AT THE
 BOTTOM OF THE FORM.
  
 C) WALL TYPES ITEM #9 IS MISSING THE ADJACENT WALL
 SEPARATING THE GARAGE FROM THE MAIN HOUSE. INSULATION
 REQUIRED. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 D) REVISE THE CLIMATE ZONE. SEE TABLE R301.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) REVISE DOORS SPECIFIED ON PAGE 3 OF 5. NEED TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SIZE SPECIFIED
 FOR THE ENTRY DOOR DOESN'T MATCH PLANS.
 NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED ON THE
 GLAZING CALCULATIONS NO DOORS. SLIDING GLASS DOORS NEED
 TO BE CONSIDERED IN WINDOWS SECTION. SEE SEC.
 R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014)
  
 F) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014)
  
 G) TABLE 402.4.1.1 SUBMITTED IS INCOMPLETE. THERE ARE
 ITEMS THAT NEED TO BE CHECKED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014)
  
 H) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE
 U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS
 ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 11- CLEARLY SPECIFY ALL DESIGN LOADS INCLUDING THE
 ATTIC LIVE LOADS AS REQUIRED BY FOOTNOTES "B" AND "G"
 OF TABLE R301.5 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 12- THE ROOF PROJECTION ON THE SOUTH SIDE NEEDS TO
 COMPLY WITH THE 1 HOUR ON THE UNDERSIDE FIRE RATING AS
 REQUIRED BY TABLE R302.1. (1) OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR THE ROOF PROJECTION ON THE SOUTH
 SIDE.
 NOTE: KEEP IN MIND THAT VENTS ON THE UNDERSIDE OF THE
 ROOF PROJECTIONS DON'T COMPLY WITH THE 1 HR FIRE
 RATING.
  
 13- SHEET A1: ARCHITECT CALLS FOR WINDOWS AND DOORS
 IMPACT GLASS FOR HURRICANE PROTECTION. PRODUCT
 APPROVALS SUBMITTED ARE NOT IMPACT GLASS. PLANS AND
 PRODUCT APPROVALS TO MATCH. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  