Plan Review Notes For Permit 15110746 |
Permit Number |
15110746 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-12-04 07:38:20 | 2ND REVIEW 2014 MECHANICAL | | PERMIT #15110746 | | 12/4/15 | | | | 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE | | THE THE AMOUNT OF SUPPLY CFM'S AT EACH DIFFUSER | | LOCATION. PLEASE NOTE THAT THE THE TRANSFER GRILLS | | SIZED AT 48 SQ. INCHES WILL ONLY RETURN 100 CFM'S OF | | SUPPLY AIR FROM THE BEDROOMS- SEE SECTION M1602.4 | | FBC-14 RESIDENTIAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|