Plan Review Notes
Plan Review Notes For Permit 15110710
Permit Number 15110710
Review Stop P
Sequence Number 1
Notes
Date Text
2016-02-03 10:06:031) SHT. A-1 - THE NOTES STATE THAT THE TOILET ROOMS
 SHALL COMPLY WITH FBC SEC. 1210 BUT THE FINISH SCHEDULE
 SHOWS THE WALLS IN THE TOILET ROOMS TO BE PAINTEED. THE
 TOILET ROOMS SHALL COMPLY WITH 2014 FBC SEC. 1210.2.2.
 2) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET IN
 THE MEN'S RESTROOM. IT APPEARS THAT THE URINAL MAY
 ENCROACCH INTO THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE WATER CLOSET ENCOACH INTO THE CLEAR
 FLOOR SPACE FOR THE URINAL. NO OTHER FIXTURES OR
 OBSTRUCTIONS SHALL BE LOCATED WITHIN THE REQUIRED WATER
 CLOSET CLEARANCE.2014 FBC-ACCESS. SEC.604.3.2.
 3) SUBMIT THE OCCUPANCY TYPE AND OCCUPANT LOAD OF THE
 SWIMMING POOL, THE POOL DECK, THE TOT LOT AND THE
 CABANA PER THE 2014 FBC SEC.303 AND TABLE 1004.1.2.
 4) THE MINIMUM REQUIRED SANITARY FACILITIES SHALL BE
 BASED UPON THE SQUARE FOOTAGE OF THE SWIMMING POOL IN
 ACCORDANCE WITH THE 2014 FBC-PLUMBING SEC. 403.6.
 SUBMIT THE SQUARE FOOTAGE OF THE SWIMMING POOL.
 5) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014 FBC-
 ACCESS. SEC.307.2 FOR PROTRUDING OBJECTS. THE HIGH SIDE
 DRINKING FOUNTAIN MAY REQUIRE A SKIRT TO HAVE THE
 LEADING EDGE BELOW 27 INCHES.
 6) PROVIDE A KEY LEGEND FOR THE KEY NOTES ON SHEETS P-1
 & P-2 .
 7) HOT OR TEMPERED WATER SHALL BE SUPPLIED TO THE
 LAVATORIES PER THE 2014 FBC-PLUMBING SEC.607.1.
 8) A SERVICE SINK MAY BE REQUIRED DEPENDING ON THE
 OCCUPANCY PER 2014 FBC-PLUMBING TABLE 403.1. IF ONE IS
 REQUIRED, HOT WATER WILL BE REQUIRED TO THE FIXTURE PER
 2014 FBC-PLUMBING SEC.607.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  