2016-02-17 07:11:42INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2008 NEC
 COMMENTS:
  
 1. PROVIDE A NOTE TO COMPLY WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE AND UPDATE ALL CODE
 REFERENCES TO NEC 2011. A NOTE WILL SUFFICE.
 2. ADD A NOTE TO INDICATE REQUIREMENTS OF NEC 700.12A
 FOR THE EM FIXTURES AND THAT THEY BE AHEAD OF ANY
 SWITCHING MECHANISM.
 3. LABEL POOL PUMP IN PANEL SCHEDULE TO BE GFCI
 PROTECTED. FBC 107 NEC 680.21C
 4. PLEASE PROVIDE AN INTERSYSTEM BONDING TERMINATION AT
 THE SERVICE ONE-LINE. NEC 250.94
 5. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  