Plan Review Notes For Permit 15110710 |
Permit Number |
15110710 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-17 07:11:42 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2008 NEC | | COMMENTS: | | | | 1. PROVIDE A NOTE TO COMPLY WITH FBC EC 405.7.3, | | 405.7.4 SEE VERBIAGE IN THE CODE AND UPDATE ALL CODE | | REFERENCES TO NEC 2011. A NOTE WILL SUFFICE. | | 2. ADD A NOTE TO INDICATE REQUIREMENTS OF NEC 700.12A | | FOR THE EM FIXTURES AND THAT THEY BE AHEAD OF ANY | | SWITCHING MECHANISM. | | 3. LABEL POOL PUMP IN PANEL SCHEDULE TO BE GFCI | | PROTECTED. FBC 107 NEC 680.21C | | 4. PLEASE PROVIDE AN INTERSYSTEM BONDING TERMINATION AT | | THE SERVICE ONE-LINE. NEC 250.94 | | 5. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|