Plan Review Notes
Plan Review Notes For Permit 15110710
Permit Number 15110710
Review Stop B
Sequence Number 1
Notes
Date Text
2016-02-04 06:55:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110710
 ADD: 5025 ERNEST ST.
 CONT: LENNAR HOMES
 TEL: 954-533-5299
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. FEB. 03/2016
 ACTION: DENIED
  
 1A) THE PERMIT WAS SUBMITTED WITH A ERNEST ST. ADDRESS.
 PLEASE PROVIDE THE CORRECT ADDRESS FOR THE RECREATIONAL
 TRACT THE POOL CABANA IS LOCATED ON. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION WHERE WORK WILL BE COMPLETED.
 THURS. FEB. 04/2016 CITY STAFF HAS ASSIGNED THE
 ADDRESS:
 4316 BRAXTON AVE. PCN: 74-42-43-11-08-018-0000
 PLEASE UPDATE THE PLANS TITLE BLOCK TO REFLECT THE
 LOCATION OF THE PROJECT.
 2014 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS NUMBERS OR LETTERS. EACH CHARACTER SHALL BE NOT
 LESS THAN 4 INCHES (102 MM) IN HEIGHT AND NOT LESS THAN
 0.5 INCH (12.7 MM) IN WIDTH. THEY SHALL BE INSTALLED ON
 A CONTRASTING BACKGROUND AND BE PLAINLY VISIBLE FROM
 THE STREET OR ROAD FRONTING THE PROPERTY
  
 1B) THERE IS NEITHER LIFE SAFETY NOR BUILDING CODE DATA
 SHEET IN THIS SUBMITTAL PROVIDING THE MINIMUM BUILDING
 TYPE, OCCUPANCY TYPE (A4) OCCUPANT LOADS, PLEASE
 PROVIDE FOR THE WHOLE OF THE ENCLOSED FENCED AREA. FOR
 THE POOL, POOL DECK AND THE TOT LOT PLEASE FIGURE 50
 SQUARE FEET PER OCCUPANT. THE FIGURE SHOULD BE WELL
 OVER 150 OCCUPANTS THAT WILL REQUIRE EGRESS. WHEN WE
 HIT OCCUPANT LOADS OF 50 AND GREATER 2 EXITS ARE
 REQUIRED.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP
 MINIMUM BUILDING TYPE
 BUILDING FIRE SPRINKLERED OR NOT
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 2) FENCING DOES REQUIRE A SEPARATE PERMIT. NOTE THE
 FENCING AND GATES ARE INCLUDED IN THE DETAILS SUBMITTED
 UNDER THE SITE PLAN AND SURVEY. PLEASE NOTE THE GATE IN
 THE FENCE SEPARATING THE POOL DECK AND TOT LOT NEEDS TO
 SWING OUT AWAY FROM THE POOL. 2014 FBC-B 454.1.3.1.9.
  
 3) IN BOTH THE POOL & POOL DECK AS WELL AS THE TOT LOT
 THE OCCUPANT LOAD WILL BE ABOVE 50 OCCUPANTS EACH AREA
 REQUIRING 2 ACCESSIBLE EXITS. 2014 FBC-B TABLE 1015.1
 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY.
 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE MEANS OF
 EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION 1007.
 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS
 REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
  
 4) THIS IS JUST NOTICE TO THE REQUIREMENTS OF THE 2014
 FBC-ACCESSIBILITY CODE 1009.1 GENERAL.
 WHERE PROVIDED, POOL LIFTS, SLOPED ENTRIES, TRANSFER
 WALLS, TRANSFER SYSTEMS, AND POOL STAIRS SHALL COMPLY
 WITH 1009.
  
 2014 FBC-ACCESSIBILITY CODE. 1009.2 POOL LIFTS. POOL
 LIFTS SHALL COMPLY WITH 1009.2.
  
 ADVISORY 1009.2 POOL LIFTS. THERE ARE A VARIETY OF
 SEATS AVAILABLE ON POOL LIFTS RANGING FROM SLING SEATS
 TO THOSE THAT ARE PREFORMED OR MOLDED. POOL LIFT SEATS
 WITH BACKS WILL ENABLE A LARGER POPULATION OF PERSONS
 WITH DISABILITIES TO USE THE LIFT. POOL LIFT SEATS THAT
 CONSIST OF MATERIALS THAT RESIST CORROSION AND PROVIDE
 A FIRM BASE TO TRANSFER WILL BE USABLE BY A WIDER RANGE
 OF PEOPLE WITH DISABILITIES. ADDITIONAL OPTIONS SUCH AS
 ARMRESTS, HEAD RESTS, SEAT BELTS, AND LEG SUPPORT WILL
 ENHANCE ACCESSIBILITY AND BETTER ACCOMMODATE PEOPLE
 WITH A WIDE RANGE OF DISABILITIES.
 1009.2.1 POOL LIFT LOCATION. POOL LIFTS SHALL BE
 LOCATED WHERE THE WATER LEVEL DOES NOT EXCEED 48 INCHES
 (1220 MM).
  
 5) SHEET 033-A-1 FLOOR PLANS THE RESTROOMS DO NOT
 INDICATE COMPLIANCE WITH THE 2014 FBC-B 454.1.6.1.1
 ONE DIAPER CHANGING TABLE SHALL BE PROVIDED AT EACH
 RESTROOM. DIAPER CHANGING TABLES ARE NOT REQUIRED AT
 RESTROOMS WHERE ALL POOLS SERVED ARE RESTRICTED TO
 ADULT USE ONLY.
  
 6) 2014 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF
 EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF
 THIS SECTION. GATES USED AS A COMPONENT IN A MEANS OF
 EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR
 DOORS.
 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A
 GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES
 WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E
 OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
 UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7) UNDER SUPPORTING DOCUMENTS THERE IS A PRODUCT
 APPROVAL FOR FIXED WINDOWS. F 1534R5 MI WINDOWS WITHIN
 THIS DOCUMENT THERE ARE SEVERAL WINDOW TYPES, PLEASE
 IDENTIFY WHICH TYPE OF WINDOW IS TO BE INSTALLED. NOTE
 THERE ARE IMPACT AND NON-IMPACT RATED WINDOWS, IF
 NON-IMPACT WINDOWS ARE TO BE INSTALLED THEN STORM
 SHUTTERS FOR OPENING PROTECTION AGAINST IMPACT WILL
 ALSO NEED TO BE SELECTED.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
 ( E ) SHUTTERS
  
 8) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) SHEET 101-S-2 SECTION 1 THROUGH THE BUILDING SHOWS
 THE MONOLITHIC FOOTER ONLY 8 INCHES BENEATH GRADE.
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 1809.4 DEPTH AND
 WIDTH OF FOOTINGS. THE MINIMUM DEPTH OF FOOTINGS BELOW
 THE UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES (305
 MM). SHEET 100-S-1 FOOTING SCHEDULE MF16A INDICATES HE
 DEPTH OF THE FOUNDATION AS 16 INCHES. PLEASE MAKE
 CORRECTION.
  
 10) SHEET 102-S-3 UNDER THE HEADING CRITERIA AND LOADS
 THE ROOF PRESSURES ARE GIVEN ASSUMED VASD NOT GIVEN,
 AND THERE ARE NO PRESSURES FOR WALL ZONES 4 & 5. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  