2016-04-18 09:35:15RESIDENTIAL (R3) ALTERATION FIFTH MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
 1- PREVIOUS MECHANICAL REVIEWS WERE DENIED BECAUSE THE
 A/C UNIT MAY HAVE BEING OVERSIZED. ENGINEER WAS
 INFORMED VIA PHONE CONVERSATION THAT THE CALCULATIONS
 NEED TO BE DONE BASED ON THE INTERIOR DESIGN
 TEMPERATURES. THE CODE REQUIRES THE A/C SIZING
 CALCULATIONS TO BE DONE BASED ON THE INTERIOR DESIGN
 TEMPERATURES OF 75 DEGREES MINIMUM FOR COOLING AND 72
 DEGREES MAXIMUM FOR HEATING AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). THE CALCULATIONS SUBMITTED DON'T SEEM TO COMPLY
 WITH THIS INTERIOR DESIGN TEMPERATURES. PAGE 1 OF 1 OF
 AIR SYSTEM SIZING SUMMARY FOR FAMILY-BEDROOMS AHU-1
 SHOWS DESIGN SUPPLY TEMP..........58.0 DEGREES.
 THEREFORE, IT DOESN'T SEEM TO COMPLY. REVISE AS
 REQUIRED.
  
 2- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1.
 EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY ITEMS #1 ABOVE. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: THE DESIGN PROFESSIONAL MAY BE CHARGED FOUR TIMES
 THE PLAN REVIEW FEE IF REVIEW IS DENIED AGAIN AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  