2016-04-18 09:35:15 | RESIDENTIAL (R3) ALTERATION FIFTH MECHANICAL REVIEW |
| CHECKLIST. |
| CODE: FBC-5TH EDITION (2014) |
| |
| 1- PREVIOUS MECHANICAL REVIEWS WERE DENIED BECAUSE THE |
| A/C UNIT MAY HAVE BEING OVERSIZED. ENGINEER WAS |
| INFORMED VIA PHONE CONVERSATION THAT THE CALCULATIONS |
| NEED TO BE DONE BASED ON THE INTERIOR DESIGN |
| TEMPERATURES. THE CODE REQUIRES THE A/C SIZING |
| CALCULATIONS TO BE DONE BASED ON THE INTERIOR DESIGN |
| TEMPERATURES OF 75 DEGREES MINIMUM FOR COOLING AND 72 |
| DEGREES MAXIMUM FOR HEATING AS REQUIRED BY SEC. |
| R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). THE CALCULATIONS SUBMITTED DON'T SEEM TO COMPLY |
| WITH THIS INTERIOR DESIGN TEMPERATURES. PAGE 1 OF 1 OF |
| AIR SYSTEM SIZING SUMMARY FOR FAMILY-BEDROOMS AHU-1 |
| SHOWS DESIGN SUPPLY TEMP..........58.0 DEGREES. |
| THEREFORE, IT DOESN'T SEEM TO COMPLY. REVISE AS |
| REQUIRED. |
| |
| 2- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1. |
| EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING |
| CALCULATIONS AS REQUIRED BY ITEMS #1 ABOVE. SEC. |
| R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| NOTE: THE DESIGN PROFESSIONAL MAY BE CHARGED FOUR TIMES |
| THE PLAN REVIEW FEE IF REVIEW IS DENIED AGAIN AS |
| REQUIRED BY FLORIDA STATUTE 553.80(2)(B). |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR |
| REFERENCE. |
| |