Plan Review Notes
Plan Review Notes For Permit 15110686
Permit Number 15110686
Review Stop M
Sequence Number 5
Notes
Date Text
2016-04-14 14:19:4604/14/16 RECEIVED AND RESPONDED E-MAIL TO MICHAEL
 BASSFORD P.E. REGARDING THE CALCULATIONS FOR THE
 EQUIPMENT SIZING.
  
 GOOD AFTERNOON MR. BASSFORD,
 DO YOU REMEMBER THAT I TOLD YOU THAT HE CODE REQUIRES
 THE CALCULATIONS TO BE DONE BASED ON THE INTERIOR
 DESIGN TEMPERATURES OF 75 DEGREES MINIMUM FOR COOLING
 AND 72 DEGREES MAXIMUM FOR HEATING AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). THE CALCULATIONS THAT YOU SUBMITTED DON'T SEEM
 TO COMPLY WITH THIS INTERIOR DESIGN TEMPERATURES.
  
 SINCERELY,
 JULIO GOMEZ
  
  
 ORIGINAL COMMENTS BELOW:
  
 RESIDENTIAL (R3) ALTERATION THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
 1- EQUIPMENT CAPACITY CAN NOT BE MORE THAN 1.15 TIMES
 THE CALCULATED LOAD. SEC. R403.6.1.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS
 SUBMITTED SHOW A TOTAL CONDITIONING LOAD OF 21454
 BTU/HR. FRONT PAGE OF CALCULATIONS SUBMITTED CALL FOR
 2.5 TONS. THIS IS NOT ALLOWED. REVISED AS REQUIRED.
 REPEAT COMMENT. 2.5 TON UNIT IS MORE THAN 1.15 TIMES
 THE CALCULATED LOAD.
  
 2- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1.
 EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY ITEMS #2 ABOVE. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 REPEAT COMMENT.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]