Plan Review Notes For Permit 15110686 |
Permit Number |
15110686 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-03-02 15:11:10 | RESIDENTIAL (R3) ALTERATION SECOND MECHANICAL REVIEW | | CHECKLIST. | | CODE: FBC-5TH EDITION (2014) | | | | 1- ENGINEER WHO SIGNED AND SEALED THE EQUIPMENT SIZING | | CALCULATIONS TO LEGIBLY PROVIDE ALL HIS INFORMATION AS | | REQUIRED BY F.A.C. SEC. 61G15-23.002(2). | | REPEAT COMMENT. | | | | 2- EQUIPMENT CAPACITY CAN NOT BE MORE THAN 1.15 TIMES | | THE CALCULATED LOAD. SEC. R403.6.1.1 OF FBC-ENERGY | | CONSERVATION, 5TH EDITION (2014). CALCULATIONS | | SUBMITTED SHOW A TOTAL CONDITIONING LOAD OF 21454 | | BTU/HR. FRONT PAGE OF CALCULATIONS SUBMITTED CALL FOR | | 2.5 TONS. THIS IS NOT ALLOWED. REVISED AS REQUIRED. | | REPEAT COMMENT. 2.5 TON UNIT IS MORE THAN 1.15 TIMES | | THE CALCULATED LOAD. | | | | 3- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1. | | EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING | | CALCULATIONS AS REQUIRED BY ITEMS #2 ABOVE. SEC. | | R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION | | (2014). | | REPEAT COMMENT. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD | | PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR | | REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|