2016-03-02 15:11:10RESIDENTIAL (R3) ALTERATION SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
 1- ENGINEER WHO SIGNED AND SEALED THE EQUIPMENT SIZING
 CALCULATIONS TO LEGIBLY PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY F.A.C. SEC. 61G15-23.002(2).
 REPEAT COMMENT.
  
 2- EQUIPMENT CAPACITY CAN NOT BE MORE THAN 1.15 TIMES
 THE CALCULATED LOAD. SEC. R403.6.1.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS
 SUBMITTED SHOW A TOTAL CONDITIONING LOAD OF 21454
 BTU/HR. FRONT PAGE OF CALCULATIONS SUBMITTED CALL FOR
 2.5 TONS. THIS IS NOT ALLOWED. REVISED AS REQUIRED.
 REPEAT COMMENT. 2.5 TON UNIT IS MORE THAN 1.15 TIMES
 THE CALCULATED LOAD.
  
 3- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1.
 EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY ITEMS #2 ABOVE. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 REPEAT COMMENT.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  