2015-12-23 15:32:14 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6700 |
| [email protected] |
| ALTERNATE CONTACT |
| MIKE ALBARRAN |
| 561-805-6746 |
| [email protected] |
| |
| |
| PROVISO |
| |
| (C) BOXES AT CEILING-SUSPENDED (PADDLE) FAN OUTLETS. |
| OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE |
| SUPPORT |
| OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE LISTED, |
| SHALL BE |
| MARKED BY THEIR MANUFACTURER AS SUITABLE FOR THIS |
| PURPOSE, |
| AND SHALL NOT SUPPORT CEILING-SUSPENDED (PADDLE) FANS |
| THAT |
| WEIGH MORE THAN 32 KG (70 LB). FOR OUTLET BOXES OR |
| OUTLET BOX |
| SYSTEMS DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) |
| FANS |
| THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| MARKING SHALL |
| INCLUDE THE MAXIMUM WEIGHT TO BE SUPPORTED. |
| |
| R404.1 LIGHTING EQUIPMENT (MANDATORY). |
| A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| EFFICACY LAMPS. |
| |
| R315.1 CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 |
| MM) OF EACH ROOM USED FOR SLEEPING PURPOSES. |
| |
| |