2015-12-22 15:52:35 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. |
| CODE: FBC-5TH EDITION (2014) |
| |
| 1- EXISTING ENCLOSED PORCH AREA IS ALTERED TO EXPAND |
| THE LIVING AREA. BRING PLANS TO PALM BEACH COUNTY (2300 |
| N. JOG RD.) FOR IMPACT FEES ASSESSMENT.. BRING BACK |
| COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES |
| ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED |
| LAND DEVELOPMENT CODE. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) THERE IS A PERMIT APPLICATION FOR ROOFING |
| SUB-PERMIT. PROVIDE PRODUCT APPROVAL FOR ROOF MATERIAL |
| TO BE INSTALLED. AND, CLEARLY IDENTIFY APPROVED |
| ASSEMBLY TO BE INSTALLED. ALSO, PROVIDE SIGNED AND |
| SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY |
| DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301 |
| OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| B) WINDOW MULLIONS AS SHOWN ON PLANS. |
| |
| C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| SUBMITTED. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH |
| SPECIFIED CONNECTOR. |
| |
| D) OUTSWING ENTRY DOOR AS SHOWN ON PLANS. DRAWINGS |
| SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL11136-R3 ARE |
| FOR "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOOR. |
| |
| E) OUTSWING KITCHEN DOOR THAT MEETS THE DESIGN |
| PRESSURES CALCULATED BY THE ENGINEER ON SHEET S.1. |
| DESIGN PRESSURES FOR DOOR SUBMITTED WITH FLORIDA |
| PRODUCT APPROVAL FL15474-R1 DON'T MEET THE CALCULATED |
| DESIGN PRESSURES. PRODUCT APPROVAL NEED TO MEET OR |
| EXCEED THE CALCULATED DESIGN PRESSURES. |
| |
| F) HURRICANE SHUTTERS FOR WINDOWS AND DOORS WITHOUT |
| IMPACT RATED GLAZING . AND, PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. SEE INSTALLATION SCHEDULE CITY |
| SAMPLE OR PROVIDE COMPLETE INSTALLATION SCHEDULE IN ANY |
| OTHER FORMAT THAT HAS ALL THE REQUIRED INFORMATION. |
| |
| 3- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| 4- WINDOW AND DOOR SCHEDULE SHOWN ON SHEET S.1 CALL FOR |
| WINDOWS AND DOORS WITH IMPACT GLAZING. PRODUCT |
| APPROVALS SUBMITTED DON'T HAVE IMPACT GLAZING. REVISE |
| AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 5- ENERGY CALCULATIONS SUBMITTED: |
| A) ENGINEER WHO SIGNED AND SEALED THE ENERGY |
| CALCULATIONS TO PROVIDE ALL HIS INFORMATION AS REQUIRED |
| BY F.A.C. SEC. 61G15-23.002 AND F.S. 471. |
| |
| B) ENGINEER WHO SIGNED AND SEALED THE ENERGY |
| CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS |
| REQUIRED BY F.A.C. SEC. 61G15-23.002. AND F.S. 471. |
| |
| C) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. SEC. |
| R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| D) ITEM #11: PROVIDE DOCUMENTATION SHOWING HOW |
| OBTAINING THE R-8 VALUE FOR DUCT. SEC. R405.4.3 OF |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| NOTE: SEE MECHANICAL NOTES ON MECHANICAL PLAN M.1. |
| |
| E) CLIMATE ZONE SHOWN ON PAGE 2 OF 4 IS INCORRECT. SEE |
| TABLE R301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014) AND REVISE AS REQUIRED. |
| |
| F) PROVIDE COMPLETE INFORMATION FOR THE WINDOWS |
| OVERHANG DEPTH AND SEPARATION. SEC. R101.5.1.1.2 OF |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| G) PROVIDE COMPLETE INFORMATION THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE |
| U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY |
| CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS |
| ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| |
| 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. REVISE VALUATION AS REQUIRED. INCLUDE THE |
| ROOFING SCOPE OF WORK. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR |
| REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |