2016-01-07 05:04:511) THERE IS A NOTE ON THE PLAN STATING THE TOTAL BTU
 LOAD IS 648,000 BTU'S AND THE TABLE SHOWS 113,000
 BTU'S.THE 648M IS OBVIOUSLY WRONG. DELETE THIS NOTE
 FROM THE PLANS.
 2) THERE IS A NOTE ON THE PLAN STATING THE TOTAL RUN IS
 100 FT. BUT THE RISER SHOWS A TOTAL RUN OF 75 FT. WHICH
 IS IT? I CANNOT CHECK PIPE SIZES UNTIL THE CORRECT
 DEVELOPED LENGTH IS PLACED ON THE PLAN. CLARIFY.
 3) THE DESCRIPTION OF WORK ON THE APPLICATION INCLUDES
 A BBQ AND A POOL HEATER. THESE APPLIANCES ARE NOT SHOWN
 ON THE RISER. REMOVE THEM FROM THE DESCRIPTION OF WORK
 ON THE PERMIT APPLICATION IF THEY ARE NOT BEING
 INSTALLED OR SHOW THE FUTURE OUTLETS AND BTU LOAD ON
 THE GAS RISER.
 4) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED
 SUPPLYING THE DRYER AND COOKTOP SHALL BE 1" PER TABLE
 402.4 (15). 2014 FUEL GAS CODE.
 5) THERE IS A NOTE ON THE PLAN THAT STATES THE INLET
 PRESSURE IS LESS THAN 2 PSI BUT THERE IS A REFERENCE ON
 THE PLAN TO GAS TABLE 402.4 (19) WHICH IS FOR A SYSTEM
 WITH AN INLET PRESSURE OF 5 PSI. THIS IS OBVIOUSLY
 WRONG.REFER TO THE CORRECT GAS TABLE FROM THE 2014 FUEL
 GAS CODE FOR THIS SYSTEM.
 6) THE PLANS ALSO REFER TO PE (POLYETHELYNE) PIPE.THERE
 IS NO PE PIPE SHOWN ON THE RISER.PE PIPE CAN ONLY BE
 INSTALLED OUTSIDE UNDERGROUND. EITHER SHOW THE PIPE AND
 LENGTH OF THE SECTION OR DELETE THIS NOTE FROM THE
 PLAN.
 7) THE 1/2" GALVANIZED LINE TO THE COOKTOP MAY BE
 UNDERSIZED PER 2014 FGC TABLE 402.4 (2) DEPENDING ON
 THE DISTANCE OF THE TOTAL DEVELOPED LENGTH.
 8) SUBMIT A LEGIBLE GAS VENT DETAIL FOR REVIEW. SUBMIT
 DETAILS FOR THE VENT FOR THE WATER HEATER IN THE
 GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF PENETRATION
 AND HOW IT IS TO BE SEALED AT THE ROOF PENETRATION,
 ETC. COMPLY WITH FGC SECS. 502 & 503.
 9) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR
 ALL THE GAS APPLIANCES.WPB AMEND. TO FBC SEC. 107.1,
 ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014 FBC
 SEC.301.3.
  
  