2016-01-07 05:04:51 | 1) THERE IS A NOTE ON THE PLAN STATING THE TOTAL BTU |
| LOAD IS 648,000 BTU'S AND THE TABLE SHOWS 113,000 |
| BTU'S.THE 648M IS OBVIOUSLY WRONG. DELETE THIS NOTE |
| FROM THE PLANS. |
| 2) THERE IS A NOTE ON THE PLAN STATING THE TOTAL RUN IS |
| 100 FT. BUT THE RISER SHOWS A TOTAL RUN OF 75 FT. WHICH |
| IS IT? I CANNOT CHECK PIPE SIZES UNTIL THE CORRECT |
| DEVELOPED LENGTH IS PLACED ON THE PLAN. CLARIFY. |
| 3) THE DESCRIPTION OF WORK ON THE APPLICATION INCLUDES |
| A BBQ AND A POOL HEATER. THESE APPLIANCES ARE NOT SHOWN |
| ON THE RISER. REMOVE THEM FROM THE DESCRIPTION OF WORK |
| ON THE PERMIT APPLICATION IF THEY ARE NOT BEING |
| INSTALLED OR SHOW THE FUTURE OUTLETS AND BTU LOAD ON |
| THE GAS RISER. |
| 4) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED |
| SUPPLYING THE DRYER AND COOKTOP SHALL BE 1" PER TABLE |
| 402.4 (15). 2014 FUEL GAS CODE. |
| 5) THERE IS A NOTE ON THE PLAN THAT STATES THE INLET |
| PRESSURE IS LESS THAN 2 PSI BUT THERE IS A REFERENCE ON |
| THE PLAN TO GAS TABLE 402.4 (19) WHICH IS FOR A SYSTEM |
| WITH AN INLET PRESSURE OF 5 PSI. THIS IS OBVIOUSLY |
| WRONG.REFER TO THE CORRECT GAS TABLE FROM THE 2014 FUEL |
| GAS CODE FOR THIS SYSTEM. |
| 6) THE PLANS ALSO REFER TO PE (POLYETHELYNE) PIPE.THERE |
| IS NO PE PIPE SHOWN ON THE RISER.PE PIPE CAN ONLY BE |
| INSTALLED OUTSIDE UNDERGROUND. EITHER SHOW THE PIPE AND |
| LENGTH OF THE SECTION OR DELETE THIS NOTE FROM THE |
| PLAN. |
| 7) THE 1/2" GALVANIZED LINE TO THE COOKTOP MAY BE |
| UNDERSIZED PER 2014 FGC TABLE 402.4 (2) DEPENDING ON |
| THE DISTANCE OF THE TOTAL DEVELOPED LENGTH. |
| 8) SUBMIT A LEGIBLE GAS VENT DETAIL FOR REVIEW. SUBMIT |
| DETAILS FOR THE VENT FOR THE WATER HEATER IN THE |
| GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF PENETRATION |
| AND HOW IT IS TO BE SEALED AT THE ROOF PENETRATION, |
| ETC. COMPLY WITH FGC SECS. 502 & 503. |
| 9) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR |
| ALL THE GAS APPLIANCES.WPB AMEND. TO FBC SEC. 107.1, |
| ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014 FBC |
| SEC.301.3. |
| |
| |