Plan Review Notes
Plan Review Notes For Permit 15110673
Permit Number 15110673
Review Stop G
Sequence Number 1
Notes
Date Text
2015-11-19 07:58:531) THE BTU LOAD OF THE APPLIANCES LISTED IN THE TABLE
 DO NOT MATCH THE BTU LOAD SHOWN ON THE GAS RISER.
 CLARIFY.
 2) THERE IS A NOTE ON THE PLAN STATING THE TOTAL BTU
 LOAD IS 648,000 BTU'S AND THE TABLE SHOWS 140,000
 BTU'S.
 3) THERE IS A NOTE ON THE PLAN STATING THE TOTAL RUN IS
 100 FT. BUT THE RISER SHOWS A TOTAL RUN OF 74 FT.
 CLARIFY.
 4) THE DESCRIPTION OF WORK ON THE APPLICATION INCLUDES
 A BBQ AND A POOL HEATER. THESE APPLIANCES ARE NOT SHOWN
 ON THE RISER. REMOVE THEM FROM THE DESCRIPTION OF WORK
 ON THE PERMIT APPLICATION IF THEY ARE NOT BEING
 INSTALLED.
 5) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED SHALL
 BE 1" PER TABLE 402.4 (15). 2014 FUEL GAS CODE.
 6) INDICATE THE CORRESPONDING EHD FOR THE CSST
 PIPING.TABLE 402.4 (15) 2014 FUEL GAS CODE.
 7) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
 8) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2, AND
 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 SEC.301.3 OF 2014 FUEL GAS CODE.
 9) IF ANY MP REGULATORS ARE GOING TO BE INSTALLED, SHOW
 THE LOCATION ON THE PLANS AND LIST THE CORRECT SIZING
 TABLE FOR THE SYSTEM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  