2016-01-07 06:20:01 | 1) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS.IT |
| APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO |
| FBC SEC. 107.1, ALL APPLIANCES SHALL BE LISTED AND |
| LABELED PER 2014 FBC FUEL GAS CODE SEC.301.3. |
| 2) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED SHALL |
| BE 1 1/4" PER TABLE 402.4(15) OF THE FGC.THIS LINE |
| SUPPLIES THE DRYER, COOKTOP, AND SUMMER KITCHEN. |
| 3) THE PE TO THE POOL HEATER SHALL BE 1 1/2 ". TABLE |
| 402.4 (21) FGC. |
| 4) THE PLANS REFER TO TABLE 402.4 (2) FOR PE PIPE. THIS |
| TABLE IS FOR SCH. 40 METALLIC PIPE. THE CORRECT TABLE |
| FROM THE GAS CODE FOR PE PIPE IS TABLE 402.4 (21). NOTE |
| THIS ON THE PLANS. |
| 5) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT SHOW |
| THAT THE RANGE IS LISTED OR LABELED PER FUEL GAS CODE |
| SEC. 301.3. THE SUBMITTED DOCUMENT IS NOTHING MORE THAN |
| AN INTERNET SALES SHEET.SUBMIT 2 COPIES OF |
| SPECIFICATIONS THAT SHOW THAT THIS APPLIANCE IS LISTED |
| AND LABELED. |
| 6) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL |
| BE ONSITE FOR THE INSPECTOR PER THE 2014 FGC SEC.305.1. |
| 7) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN |
| THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF |
| PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF |
| PENETRATION, ETC. THE PRINTING ON THE DETAIL IS ALSO |
| TOO SMALL TO READ.WPB AMEND. TO FBC SEC. 107.2.1, FGC |
| SEC. 502 & 503. |
| 8) THERE IS A NOTE ON THE PLAN STATING THE TOTAL BTU |
| LOAD IS 648,000 BTU'S AND THE TABLE SHOWS 568,000 |
| BTU'S.THE 648M IS OBVIOUSLY WRONG. DELETE THIS NOTE |
| FROM THE PLANS. |
| 9) THERE IS A NOTE ON THE PLAN THAT STATES THE INLET |
| PRESSURE IS LESS THAN 2 PSI BUT THERE IS A REFERENCE ON |
| THE PLAN TO GAS TABLE 402.4 (19) WHICH IS FOR A SYSTEM |
| WITH AN INLET PRESSURE OF 5 PSI. THIS IS OBVIOUSLY |
| WRONG.REFER TO THE CORRECT GAS TABLE FROM THE 2014 FUEL |
| GAS CODE FOR THIS SYSTEM. |
| |