Plan Review Notes
Plan Review Notes For Permit 15110671
Permit Number 15110671
Review Stop G
Sequence Number 1
Notes
Date Text
2015-11-19 06:25:091) SHOW THE EHD NUMBER OF THE CSST FOR EACH PIPE SIZE
 BEING USED.WPB AMENDMENTS TO FBC SEC. 107.2.1.
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR ALL GAS
 APPLIANCES LOCATED ON THE INTERIOR OF THE STRUCTURE.
 COMPLY W/2010 FBC-RESIDENTIAL SEC.G2407.1 & G2407.5
 THROUGH G2407.11.
 3) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS.IT
 APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO
 FBC SEC. 107.1, ALL APPLIANCES SHALL BE LISTED AND
 LABELED PER 2014 FBCR SEC.G2404.3.
 4) THE 1/2 " GALVANIZED DROP TO THE SUMMER KITCHEN
 SHALL BE 3/4". TABLE 402.4(2) FGC.
 5) THE 1/2" CSST TO THE SUMMER KITCHEN SHALL BE 3/4".
 TABLE 402.4(15) FGC.
 6) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED SHALL
 BE 1". TABLE 402.4(15) FGC.
 7) THE PE TO THE POOL HEATER SHALL BE 1 1/2 ". TABLE
 402.4 (21) FGC.
 8) THE PLANS REFER TO TABLE 402.4 (2) FOR PE PIPE. THIS
 TABLE IS FOR SCH. 40 METALLIC PIPE. INDICATE THE
 CORRECT SIZING TABLES FOR ALL THE DIFFERENT TYPE OF
 PIPE MATERIAL ON THE PLANS.
 9) IF ANY MP REGULATORS ARE GOING TO BE INSTALLED, SHOW
 THE LOCATION ON THE PLANS AND LIST THE CORRECT SIZING
 TABLE FOR THE SYSTEM.
 10) THE BTU LOAD OF THE APPLIANCES ON THE GAS TABLE DO
 NOT CORRELATE WITH THE RISER DIAGRAM. CLARIFY.
 11) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT
 SHOW THAT THE RANGE IS LISTED OR LABELED PER 2010
 FBC-RES. SEC. G2404.3. THE SUBMITTED DOCUMENT IS
 NOTHING MORE THAN AN INTERNET SALES SHEET.
 12) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT
 SHALL BE ONSITE FOR THE INSPECTOR PER THE 2010 FBC-RES.
 SEC. G 2408.1.
 13) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN
 THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF
 PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF
 PENETRATION, ETC. COMPLY WITH 2010 FBC-RES.SECS.G2426 &
 G2427.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  