Plan Review Notes
Plan Review Notes For Permit 15110657
Permit Number 15110657
Review Stop G
Sequence Number 1
Notes
Date Text
2015-11-17 05:56:141) SUBMIT THE SIZING TABLE FROM THE 2014 FBC- FUEL GAS
 FOR THE PE PIPE.WPB AMEND. TO FBC SEC. 107.3.5.3.
 2) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE BRANCH
 LINE TO THE TANKLESS WATER HEATER BY THE KITCHEN AND
 ALSO FOR THE POOL HEATER. WPB AMEND. TO FBC SEC.
 107.3.5.3.
 3) INDICATE THE LENGTH OF THE SECTION OF PE PIPE TO THE
 TANKLESS WATER HEATER BY THE KITCHEN. WPB AMEND. TO FBC
 SEC. 107.3.5.3.
 4) SHOW THE CORRESPONDING EHD FOR THE PIPE SIZES OF THE
 CSST.REFER TO TABLE 402.4 (15) OF THE 2014 FGC.
 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT SHOWING IT IS LISTED AND LABELED PER 2014
 FGC SEC. 301.3.
 6) 2014 FBC-ENERGY ? SEC. R403.9.1.1 ? ALL GAS AND SPA
 HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82 %
 FOR HEATERS MANUFACTURED ON OR AFTER APRIL 16, 2013
 WHEN TESTED IN ACCORDANCE WITH ANSI Z 21.56. POOL
 HEATERS FIRED BY NATURAL OR LP GAS SHALL NOT HAVE
 CONTINUOUSLY BURNING PILOT LIGHTS. THE SUBMITTED
 SPECIFICATIONS SHALL SHOW PROOF OF COMPLIANCE.
 7) THE DEVELOPED LENGTH FO THE 2 PSI SYSTEM IS 127
 FEET, NOT 122 FEET WHICH MEANS THE NEXT ROW FOR THE
 LENGTH TO BE USED FOR SIZING THIS LINE IS 150 FT. THE 5
 FEET FROM THE METER DOES NOT APPEAR TO HAVE BEEN
 INCLUDED. THIS MEANS THE 3/4 " PE PIPE UP TO THE FIRST
 BRANCH TO THE TWH, COOKTOP & DRYER IS UNDRSIZED AND
 NEEDS TO BE 1 INCH IN SIZE. PER TABLE 402.4 (22) THE
 MAXIMUM BTU LOAD ON 3/4" PIPE AT 150 FEET IS 860 BTU'S
 AND THE TOTAL ON THIS LINE IS 871 BTU'S.
 8) THE MANUFACTURER'S INSTALLATION INSTRUCTIONS SHALL
 BE AVAILABLE ON THE JOBSITE AT THE TIME OF INSPECTION.
 2014 FBC-FUEL GAS SEC.305.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  