2015-11-23 07:44:42 | 1ST REVIEW 2014 MECHANICAL |
| PERMIT #15110637 |
| 11/23/15 |
| |
| 1) IN ACCORDANCE WITH SECTION 202 FBC-14 ENERGY |
| CONSERVATION, THE PROPOSED PROJECT IS DEFINED AS A |
| "RENOVATION" AND SHALL BE IN COMPLIANCE WITH THE |
| CURRENT FL. ENERGY CODE. PLEASE SEE SECTION C101.4.3 |
| AND SUBMIT ENERGY CALCULATIONS PER SECTION C101.5.1. |
| 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| AND PROVIDE VENTILATION CALCULATIONS- SEE ASHRAE 62 |
| INDOOR AIR QUALITY PROCEDURE AND TABLE 403.3 FBC-14 |
| MECHANICAL. INDICATE ON THE PLAN THE REQUIRED CFM'S OF |
| OUTSIDE AIR FOR ALL ROOMS AND SPACES, AND THE AMOUNT OF |
| O/A CFM'S PROVIDED BY THE EXISTING AC SYSTEMS. PROVIDE |
| DETAILS AND DRAWINGS FOR ALL REQUIRED UPGRADES IN THE |
| EVENT THE EXISTING SYSTEMS ARE NOT CAPABLE OF |
| SUPPORTING THE NEW OCCUPANCIES. PLEASE NOTE REFERENCE |
| IS MADE TO DOCTOR'S OFFICES ON SHEET M2, HOWEVER THE |
| PLANS DON'T INDICATE ANY DOCTOR'S OFFICES. |
| 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE EXISTING AC |
| SYSTEMS ON THE PLAN, AND CLARIFY IF THEY ARE EQUIPPED |
| WITH DUCT SMOKE DETECTORS. PROVIDE A SEQUENCE OF |
| OPERATION FOR THE DEVICES IF APPLICABLE. |
| 4) INDICATE ON THE PLAN HOW ACCESS TO THE AC AIR |
| HANDLERS WILL BE PROVIDED FOR SERVICE, REPAIR, OR |
| REPLACEMENT- SEE SECTION 306.1 FBC-14 MECHANICAL. |
| 5) PROVIDE A DETAIL ON THE PLAN FOR INSTALLATION OF THE |
| FIRE DAMPERS PER MANUFACTURER'S SPECIFICATIONS, AND |
| SUBMIT CUT SHEETS REVIEWED AND APPROVED BY THE ENGINEER |
| OF RECORD. INDICATE HOW THE DAMPERS WILL BE ACTUATED- |
| SEE SECTION 607.3.3, AND CLARIFY IF THEY WILL BE LINKED |
| TO A FIRE ALARM SYSTEM. |
| 6) INDICATE ON THE PLANS HOW ACCESS TO THE FIRE DAMPERS |
| FOR SERVICE AND MAINTRENANCE WILL BE PROVIDED, AND SHOW |
| ACCESS DOOR LOCATIONS. |
| 7) REFER TO SECTION 3006.2 FBC-14 BUILDING CODE AND |
| PROVIDE INDEPENDENT VENTILATION SYSTEMS FOR THE IT |
| ROOMS IF SOLID STATE EQUIPMENT FOR THE ELEVATORS IS |
| BEING HOUSED IN THOSE ADJACENT ROOMS. |
| 8) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE |
| DOWN OF THE NEW AC O/A INTAKE VENTILATOR, AND THE |
| TOILET ROOM EXHAUST VENTILATOR ON THE ROOF. SUBMIT CUT |
| SHEETS, AND NOA'S OR FL. PRODUCT APPROVALS FOR THE |
| VENTILATORS REVIEWED AND APPROVED BY THE ENGINEER OF |
| RECORD. |
| 9) PLEASE NOTE ADDITIONAL MECHANICAL COMMENTS MAY |
| FOLLOW RESPONSES TO ALL BUILDING DEPARTMENT REVIEWS. |
| |
| CHRISTOPHER L. COLE |