Plan Review Notes
Plan Review Notes For Permit 15110637
Permit Number 15110637
Review Stop M
Sequence Number 1
Notes
Date Text
2015-11-23 07:44:421ST REVIEW 2014 MECHANICAL
 PERMIT #15110637
 11/23/15
  
 1) IN ACCORDANCE WITH SECTION 202 FBC-14 ENERGY
 CONSERVATION, THE PROPOSED PROJECT IS DEFINED AS A
 "RENOVATION" AND SHALL BE IN COMPLIANCE WITH THE
 CURRENT FL. ENERGY CODE. PLEASE SEE SECTION C101.4.3
 AND SUBMIT ENERGY CALCULATIONS PER SECTION C101.5.1.
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE VENTILATION CALCULATIONS- SEE ASHRAE 62
 INDOOR AIR QUALITY PROCEDURE AND TABLE 403.3 FBC-14
 MECHANICAL. INDICATE ON THE PLAN THE REQUIRED CFM'S OF
 OUTSIDE AIR FOR ALL ROOMS AND SPACES, AND THE AMOUNT OF
 O/A CFM'S PROVIDED BY THE EXISTING AC SYSTEMS. PROVIDE
 DETAILS AND DRAWINGS FOR ALL REQUIRED UPGRADES IN THE
 EVENT THE EXISTING SYSTEMS ARE NOT CAPABLE OF
 SUPPORTING THE NEW OCCUPANCIES. PLEASE NOTE REFERENCE
 IS MADE TO DOCTOR'S OFFICES ON SHEET M2, HOWEVER THE
 PLANS DON'T INDICATE ANY DOCTOR'S OFFICES.
 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE EXISTING AC
 SYSTEMS ON THE PLAN, AND CLARIFY IF THEY ARE EQUIPPED
 WITH DUCT SMOKE DETECTORS. PROVIDE A SEQUENCE OF
 OPERATION FOR THE DEVICES IF APPLICABLE.
 4) INDICATE ON THE PLAN HOW ACCESS TO THE AC AIR
 HANDLERS WILL BE PROVIDED FOR SERVICE, REPAIR, OR
 REPLACEMENT- SEE SECTION 306.1 FBC-14 MECHANICAL.
 5) PROVIDE A DETAIL ON THE PLAN FOR INSTALLATION OF THE
 FIRE DAMPERS PER MANUFACTURER'S SPECIFICATIONS, AND
 SUBMIT CUT SHEETS REVIEWED AND APPROVED BY THE ENGINEER
 OF RECORD. INDICATE HOW THE DAMPERS WILL BE ACTUATED-
 SEE SECTION 607.3.3, AND CLARIFY IF THEY WILL BE LINKED
 TO A FIRE ALARM SYSTEM.
 6) INDICATE ON THE PLANS HOW ACCESS TO THE FIRE DAMPERS
 FOR SERVICE AND MAINTRENANCE WILL BE PROVIDED, AND SHOW
 ACCESS DOOR LOCATIONS.
 7) REFER TO SECTION 3006.2 FBC-14 BUILDING CODE AND
 PROVIDE INDEPENDENT VENTILATION SYSTEMS FOR THE IT
 ROOMS IF SOLID STATE EQUIPMENT FOR THE ELEVATORS IS
 BEING HOUSED IN THOSE ADJACENT ROOMS.
 8) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE
 DOWN OF THE NEW AC O/A INTAKE VENTILATOR, AND THE
 TOILET ROOM EXHAUST VENTILATOR ON THE ROOF. SUBMIT CUT
 SHEETS, AND NOA'S OR FL. PRODUCT APPROVALS FOR THE
 VENTILATORS REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD.
 9) PLEASE NOTE ADDITIONAL MECHANICAL COMMENTS MAY
 FOLLOW RESPONSES TO ALL BUILDING DEPARTMENT REVIEWS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  