Notes
Date Text
2015-12-23 10:25:151ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 PLEASE FOLLOW UP ON BUILDING AND FIRE COMMENTS IN ORDER
 TO COMPLY WITH THE ELECTRICAL REVIEW.
 PROVIDE EXISTING INFORMATION OF RISER DIAGRAM AND LOAD
 CALCS , WIRE SIZES , INSULATION TYPE , CONDUIT SIZES ,
 AND ETC.
 PROVIDE A NARRATIVE DETAILED SCOPE OF WORK. WPB FBC
 107.2.1
 AIC CALCULATIONS REQUIRED FOR 400 AMP DISCONNECT TO
 HOUSE PANELS. ( CURRENT LIMITING FUSES ? )
  
 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT CURRENT
 RATINGS,
 AND OTHER CHARACTERISTICS. THE OVERCURRENT PROTECTIVE
 DEVICES, THE TOTAL IMPEDANCE, THE EQUIPMENT
 SHORTCIRCUIT
 CURRENT RATINGS, AND OTHER CHARACTERISTICS OF THE
 CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND
 COORDINATED TO
 PERMIT THE CIRCUIT PROTECTIVE DEVICES USED TO CLEAR A
 FAULT TO
 DO SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL
 EQUIPMENT
 OF THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE
 EITHER BETWEEN
 TWO OR MORE OF THE CIRCUIT CONDUCTORS OR BETWEEN ANY
 CIRCUIT CONDUCTOR AND THE EQUIPMENT GROUNDING
 CONDUCTOR(
 S) PERMITTED IN 250.118. LISTED EQUIPMENT APPLIED IN
 ACCORDANCE WITH THEIR LISTING SHALL BE CONSIDERED TO
 MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 110.15 HIGH-LEG MARKING. ON A 4-WIRE, DELTA-CONNECTED
 SYSTEM WHERE THE MIDPOINT OF ONE PHASE WINDING IS
 GROUNDED, ONLY THE CONDUCTOR OR BUSBAR HAVING THE
 HIGHER
 PHASE VOLTAGE TO GROUND SHALL BE DURABLY AND
 PERMANENTLY
 MARKED BY AN OUTER FINISH THAT IS ORANGE IN COLOR OR BY
 OTHER
 EFFECTIVE MEANS. SUCH IDENTIFICATION SHALL BE PLACED AT
 EACH
 POINT ON THE SYSTEM WHERE A CONNECTION IS MADE IF THE
 GROUNDED CONDUCTOR IS ALSO PRESENT.
  
 PLEASE PROVIDE ADEQUATE WIRE GUTTER SIZES ACCORDING TO
 NEC
  
 (A) DEFLECTED INSULATED CONDUCTORS. WHERE INSULATED
 CONDUCTORS
 ARE DEFLECTED WITHIN AN AUXILIARY GUTTER, EITHER AT THE
 ENDS OR WHERE CONDUITS, FITTINGS, OR OTHER RACEWAYS OR
 CABLES
 ENTER OR LEAVE THE GUTTER, OR WHERE THE DIRECTION OF
 THE GUTTER IS
 DEFLECTED GREATER THAN 30 DEGREES, DIMENSIONS
 CORRESPONDING
 TO ONE WIRE PER TERMINAL IN TABLE 312.6(A) SHALL APPLY.
 (B) AUXILIARY GUTTERS USED AS PULL BOXES. WHERE
 INSULATED
 CONDUCTORS 4 AWG OR LARGER ARE PULLED THROUGH AN
 AUXILIARY
 GUTTER, THE DISTANCE BETWEEN RACEWAY AND CABLE ENTRIES
 ENCLOSING THE SAME CONDUCTOR SHALL NOT BE LESS THAN
 THAT REQUIRED
 IN 314.28(A)(1) FOR STRAIGHT PULLS AND 314.28(A)(2) FOR
 ANGLE PULLS.