2015-11-30 15:52:58 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6700 |
| [email protected] |
| ALTERNATE CONTACT |
| PHIL PETTY |
| 561-805-6742 |
| [email protected] |
| |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| PLEASE PROVIDE RELATIVE LOCATIONS OF EQUIPMENT ON PLANS |
| , PLEASE PROVIDE EXISTING CONDUIT SIZES. |
| PLEASE EXPLAIN WHY RUNNING 4 AWG FOR SUM PORTIONS AND 8 |
| AWG FOR OTHERS ? ( NEC RECCOMENDS 3 % VOLTAGE DROP ) |
| PLEASE PROVIDE MANUFACTURE SPECS OF ELECTRIC CAR |
| CHARGER. |