Notes
Date Text
2015-11-18 08:08:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110616
 ADD: 518 35TH ST.
 CONT: GARABAR
 TEL: 561-337-6798
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. NOV. 18/2015
 ACTION: DENIED
  
 1) THE PROPERTY APPRAISERS OFFICE LIST THE BUILDING
 IMPROVEMENT VALUE OF $381,913.00 DOLLARS. PLEASE
 PROVIDE DOCUMENTATION OF CODE COMPLIANCE FOR
 2014 EXISTING BUILDING CODE 706.3.2 ROOF DIAPHRAGMS
 RESISTING WIND LOADS IN HIGH-WIND REGIONS. WHERE
 ROOFING MATERIALS ARE REMOVED FROM MORE THAN 50 PERCENT
 OF THE ROOF DIAPHRAGM OR SECTION OF A BUILDING LOCATED
 WHERE THE ULTIMATE DESIGN WIND SPEED, VULT, IS GREATER
 THAN 115 MPH, AS DEFINED IN SECTION 1609 (THE HVHZ
 SHALL COMPLY WITH SECTION 1620) OF THE FLORIDA BUILDING
 CODE, BUILDING, ROOF DIAPHRAGMS, CONNECTIONS OF THE
 ROOF DIAPHRAGM TO ROOF FRAMING MEMBERS, AND
 ROOF-TO-WALL CONNECTIONS SHALL BE EVALUATED FOR THE
 WIND LOADS SPECIFIED IN THE FLORIDA BUILDING CODE,
 BUILDING, INCLUDING WIND UPLIFT. IF THE DIAPHRAGMS AND
 CONNECTIONS IN THEIR CURRENT CONDITION ARE NOT CAPABLE
 OF RESISTING AT LEAST 75 PERCENT OF THOSE WIND LOADS,
 THEY SHALL BE REPLACED OR STRENGTHENED IN ACCORDANCE
 WITH THE LOADS SPECIFIED IN THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2) THE PRODUCT APPROVAL FOR THE FLAT ROOF THAT WAS
 SUBMITTED FL16709-R2 HIGH LIGHTED PAGE 13 EXPOSURE C
 OPEN @ 0-15 FT, PLEASE UPDATE, EXPOSURE C,
 2 STORY ENCLOSED STRUCTURE, SUPPLY A NEW PAGE 13
 HIGHLIGHT THE W5 SUB-SYSTEM FOR ROOF ZONE 1, AND FOR
 ROOF ZONES 2 & 3 HIGHLIGHT PAGE 14 ENCLOSED BUILDING
 15-20 FT/ 170 MPH VULT.
  
 3) PLEASE PROVIDE A ROOFING PLAN SHOW SLOPED ROOFS AND
 FLAT ROOFS PLEASE IDENTIFY WHERE SOLOTUBE SKYLIGHT WILL
 BE LOCATED, IN WHAT ROOF ZONE 1, 2 OR 3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  