2015-11-18 08:08:08 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15110616 |
| ADD: 518 35TH ST. |
| CONT: GARABAR |
| TEL: 561-337-6798 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| 1ST REVIEW |
| DATE: WED. NOV. 18/2015 |
| ACTION: DENIED |
| |
| 1) THE PROPERTY APPRAISERS OFFICE LIST THE BUILDING |
| IMPROVEMENT VALUE OF $381,913.00 DOLLARS. PLEASE |
| PROVIDE DOCUMENTATION OF CODE COMPLIANCE FOR |
| 2014 EXISTING BUILDING CODE 706.3.2 ROOF DIAPHRAGMS |
| RESISTING WIND LOADS IN HIGH-WIND REGIONS. WHERE |
| ROOFING MATERIALS ARE REMOVED FROM MORE THAN 50 PERCENT |
| OF THE ROOF DIAPHRAGM OR SECTION OF A BUILDING LOCATED |
| WHERE THE ULTIMATE DESIGN WIND SPEED, VULT, IS GREATER |
| THAN 115 MPH, AS DEFINED IN SECTION 1609 (THE HVHZ |
| SHALL COMPLY WITH SECTION 1620) OF THE FLORIDA BUILDING |
| CODE, BUILDING, ROOF DIAPHRAGMS, CONNECTIONS OF THE |
| ROOF DIAPHRAGM TO ROOF FRAMING MEMBERS, AND |
| ROOF-TO-WALL CONNECTIONS SHALL BE EVALUATED FOR THE |
| WIND LOADS SPECIFIED IN THE FLORIDA BUILDING CODE, |
| BUILDING, INCLUDING WIND UPLIFT. IF THE DIAPHRAGMS AND |
| CONNECTIONS IN THEIR CURRENT CONDITION ARE NOT CAPABLE |
| OF RESISTING AT LEAST 75 PERCENT OF THOSE WIND LOADS, |
| THEY SHALL BE REPLACED OR STRENGTHENED IN ACCORDANCE |
| WITH THE LOADS SPECIFIED IN THE FLORIDA BUILDING CODE, |
| BUILDING. |
| |
| 2) THE PRODUCT APPROVAL FOR THE FLAT ROOF THAT WAS |
| SUBMITTED FL16709-R2 HIGH LIGHTED PAGE 13 EXPOSURE C |
| OPEN @ 0-15 FT, PLEASE UPDATE, EXPOSURE C, |
| 2 STORY ENCLOSED STRUCTURE, SUPPLY A NEW PAGE 13 |
| HIGHLIGHT THE W5 SUB-SYSTEM FOR ROOF ZONE 1, AND FOR |
| ROOF ZONES 2 & 3 HIGHLIGHT PAGE 14 ENCLOSED BUILDING |
| 15-20 FT/ 170 MPH VULT. |
| |
| 3) PLEASE PROVIDE A ROOFING PLAN SHOW SLOPED ROOFS AND |
| FLAT ROOFS PLEASE IDENTIFY WHERE SOLOTUBE SKYLIGHT WILL |
| BE LOCATED, IN WHAT ROOF ZONE 1, 2 OR 3. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |