Plan Review Notes For Permit 15110567 |
Permit Number |
15110567 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-11-19 15:29:29 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6700 | | [email protected] | | | | | | | | PLEASE SHOW DISCONNECTING MEANS ACCORDING TO NEC 230 | | PLEASE SHOW INTERSYSTEM BONDING AND WATER BONDING PER | | NEC 250 | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | FLOOR PLAN. | | NEC 240.24 (A) & (B) PANELS SHALL BE LOCATED SUCH THAT | | OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT OCCUPANTS | | SHALL HAVE ACCESS TO OCP DEVICES. |
|