Plan Review Notes
Plan Review Notes For Permit 15110553
Permit Number 15110553
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-17 16:59:32BUILDING PLAN REVIEW
 W. P. B. REVISION: 15110553
 W. P. B. PERMIT 15061093
 ADD: 319 CLEMATIS ST. SUITE # 608
 CONT: BUTLER
 TEL: 561-644-9537
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: TUES. NOV. 17/2015
 ACTION: BUILDING PROVISO
  
 1) SHEET A1.3 THE FURNITURE FLOOR PLAN AND SHEET E1.1
 BOTH INDICATE THE CONCRETE FLOOR IS TO BE CORE DRILLED
 (X-RAY SLAB FOR STEEL LOCATION) FOR THE INSTALATION OF
 ELECTRICAL AND DATA FLOOR BOXES. THE DESIGNER OF RECORD
 HAS SUBMITTED IEGRAND WIREMOLD CHICAGO APPROVED POKE
 THROU FLOOR BOXES. CONTRACTOR AND DESIGNER ARE TO
 DECIDE WHICH SERIES OF FLOOR BOXES ARE TO BE INSTALLED
 AND SUBMIT THE UL FIRE RESISTANCE ASSEMBLY THAT WILL
 PERTAIN TO THIS TYPE OF APPLICATION AND TYPE OF
 MATERIALS NEEDED TO MAINTAIN A 2 HOUR FIRE RATING OF
 THE FLOOR. 2010 FBC-B 713.4.1.2 MEMBRANE PENETRATIONS.
 PENETRATIONS OF MEMBRANES THAT ARE PART OF A HORIZONTAL
 ASSEMBLY SHALL COMPLY WITH SECTION 713.4.1.1.1 OR
 713.4.1.1.2. WHERE FLOOR/CEILING ASSEMBLIES ARE
 REQUIRED TO HAVE A FIRE-RESISTANCE RATING, RECESSED
 FIXTURES SHALL BE INSTALLED SUCH THAT THE REQUIRED FIRE
 RESISTANCE WILL NOT BE REDUCED. SUBMIT TO THE DESIGNER
 OF RECORD FOR REVIEW BEFORE SUBMITING TO THE BUILDING
 DEPARTMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  