2015-11-17 16:59:32 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 15110553 |
| W. P. B. PERMIT 15061093 |
| ADD: 319 CLEMATIS ST. SUITE # 608 |
| CONT: BUTLER |
| TEL: 561-644-9537 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| 1ST REVIEW |
| DATE: TUES. NOV. 17/2015 |
| ACTION: BUILDING PROVISO |
| |
| 1) SHEET A1.3 THE FURNITURE FLOOR PLAN AND SHEET E1.1 |
| BOTH INDICATE THE CONCRETE FLOOR IS TO BE CORE DRILLED |
| (X-RAY SLAB FOR STEEL LOCATION) FOR THE INSTALATION OF |
| ELECTRICAL AND DATA FLOOR BOXES. THE DESIGNER OF RECORD |
| HAS SUBMITTED IEGRAND WIREMOLD CHICAGO APPROVED POKE |
| THROU FLOOR BOXES. CONTRACTOR AND DESIGNER ARE TO |
| DECIDE WHICH SERIES OF FLOOR BOXES ARE TO BE INSTALLED |
| AND SUBMIT THE UL FIRE RESISTANCE ASSEMBLY THAT WILL |
| PERTAIN TO THIS TYPE OF APPLICATION AND TYPE OF |
| MATERIALS NEEDED TO MAINTAIN A 2 HOUR FIRE RATING OF |
| THE FLOOR. 2010 FBC-B 713.4.1.2 MEMBRANE PENETRATIONS. |
| PENETRATIONS OF MEMBRANES THAT ARE PART OF A HORIZONTAL |
| ASSEMBLY SHALL COMPLY WITH SECTION 713.4.1.1.1 OR |
| 713.4.1.1.2. WHERE FLOOR/CEILING ASSEMBLIES ARE |
| REQUIRED TO HAVE A FIRE-RESISTANCE RATING, RECESSED |
| FIXTURES SHALL BE INSTALLED SUCH THAT THE REQUIRED FIRE |
| RESISTANCE WILL NOT BE REDUCED. SUBMIT TO THE DESIGNER |
| OF RECORD FOR REVIEW BEFORE SUBMITING TO THE BUILDING |
| DEPARTMENT. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |