Plan Review Notes For Permit 15110532 |
Permit Number |
15110532 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-12-19 08:55:39 | 1) SHT. A001 - THE OCCUPANCY CLASSIFICATION SHOWN ON | | THE PLAN IS R-3.THIS IS NOT CORRECT. THE CORRECT | | OCCUPANCY SHALL BE PLACED ON THE PLAN IN ACCORDANCE | | WITH 2014 FBC SEC. 302. | | 2) CLEARLY SHOW THE TYPE AND LOCATION OF THE BACKFLOW | | PREVENTION DEVICE REQUIRED ON THE WATER SERVICE. THE | | DEVICE SHALL BE LOCATED AT THE METER.THE BACKFLOW | | PREVENTION DEVICE SHALL BE LEAD FREE. SUBMIT | | SPECIFICATIONS ON THE DEVICE TO BE INSTALLED. WPB | | AMEND. TO FBC SEC. 107.2.1. | | 3) INDICATE ON THE PLANS ( BOTH SETS ) THAT A WATER | | COOLER TOWER AND BOTTLED WATER WILL BE PROVIDED IN THE | | MODULAR STRUCTURE. FLAT BOTTOM CUPS SHALL BE PROVIDED | | AND A CUP DISPENSER MOUNTED IN COMPLIANCE WITH SEC. 308 | | OF THE 2014 FBC - ACCESSIBILITY SHALL BE PROVIDED. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|