Plan Review Notes
Plan Review Notes For Permit 15110532
Permit Number 15110532
Review Stop P
Sequence Number 2
Notes
Date Text
2015-12-19 08:55:391) SHT. A001 - THE OCCUPANCY CLASSIFICATION SHOWN ON
 THE PLAN IS R-3.THIS IS NOT CORRECT. THE CORRECT
 OCCUPANCY SHALL BE PLACED ON THE PLAN IN ACCORDANCE
 WITH 2014 FBC SEC. 302.
 2) CLEARLY SHOW THE TYPE AND LOCATION OF THE BACKFLOW
 PREVENTION DEVICE REQUIRED ON THE WATER SERVICE. THE
 DEVICE SHALL BE LOCATED AT THE METER.THE BACKFLOW
 PREVENTION DEVICE SHALL BE LEAD FREE. SUBMIT
 SPECIFICATIONS ON THE DEVICE TO BE INSTALLED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) INDICATE ON THE PLANS ( BOTH SETS ) THAT A WATER
 COOLER TOWER AND BOTTLED WATER WILL BE PROVIDED IN THE
 MODULAR STRUCTURE. FLAT BOTTOM CUPS SHALL BE PROVIDED
 AND A CUP DISPENSER MOUNTED IN COMPLIANCE WITH SEC. 308
 OF THE 2014 FBC - ACCESSIBILITY SHALL BE PROVIDED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  