Plan Review Notes For Permit 15110532 |
Permit Number |
15110532 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-11 10:53:00 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15110532 | | 01/11/16 | | | | 1) PLEASE CLARIFY THE OCCUPANCY CLASSIFCATION OF THE | | PROPOSED TEMPORARY CLUBHOUSE AND PROVIDE MINIMUM | | VENTILATION CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 | | FBC-14 MECHANICAL. INDICATE THE REQUIRED AND PROVIDED | | AMOUNTS OF OUTDOOR AIR CFM'S ON THE PLAN. | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | 3-TON AC SYSTEMS- REFER TO SECTION C403.2.1 FBC-14 | | ENERGY CONSERVATION. | | 3) PROVIDE DOCUMENTATION OF ENERGY EFFICIENCY | | COMPLIANCE USING EITHER THE PRESCRIPTIVE OR PERFORMANCE | | COMPLIANCE PATH- REFER TO SECTION C101.5.1 FBC-14 | | ENERGY CONSERVATION. | | 4) PROVIDE AN AC LAYOUT PLAN AND AIR DISTRIBUTION | | SCHEDULE. INCLUDE THE SUPPLY AND RETURN DUCT RUNS, DUCT | | TYPES AND SIZES, CFM CAPACITIES AT EACH SUPPLY DIFFUSER | | OR RETURN GRILL. | | 5) THE PLANS INDICATE THREE 3-TON SYSTEMS COMMUNICATING | | WITH EACH OTHER AND EXCEEDING 2000 CFM'S: SEE SECTION | | 606.2.2 AND PROVIDE DUCT SMOKE DETECTORS IN THE RETURN | | AIR SYSTEM(S). SHOW THE LOCATIONS OF THE DEVICES ON THE | | LAYOUT PLAN AND INDICATE CONTROLS OPERATION AND THE | | MEANS OF SUPERVISION- SECTIONS 606.4 & 606.4.1. | | 6) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE AC | | UNITS ON THE EXTERIOR WALL OF THE MODULAR STRUCTURE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|