Plan Review Notes
Plan Review Notes For Permit 15110532
Permit Number 15110532
Review Stop M
Sequence Number 1
Notes
Date Text
2016-01-11 10:53:001ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110532
 01/11/16
  
 1) PLEASE CLARIFY THE OCCUPANCY CLASSIFCATION OF THE
 PROPOSED TEMPORARY CLUBHOUSE AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS IN ACCORDANCE WITH TABLE 403.3
 FBC-14 MECHANICAL. INDICATE THE REQUIRED AND PROVIDED
 AMOUNTS OF OUTDOOR AIR CFM'S ON THE PLAN.
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 3-TON AC SYSTEMS- REFER TO SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION.
 3) PROVIDE DOCUMENTATION OF ENERGY EFFICIENCY
 COMPLIANCE USING EITHER THE PRESCRIPTIVE OR PERFORMANCE
 COMPLIANCE PATH- REFER TO SECTION C101.5.1 FBC-14
 ENERGY CONSERVATION.
 4) PROVIDE AN AC LAYOUT PLAN AND AIR DISTRIBUTION
 SCHEDULE. INCLUDE THE SUPPLY AND RETURN DUCT RUNS, DUCT
 TYPES AND SIZES, CFM CAPACITIES AT EACH SUPPLY DIFFUSER
 OR RETURN GRILL.
 5) THE PLANS INDICATE THREE 3-TON SYSTEMS COMMUNICATING
 WITH EACH OTHER AND EXCEEDING 2000 CFM'S: SEE SECTION
 606.2.2 AND PROVIDE DUCT SMOKE DETECTORS IN THE RETURN
 AIR SYSTEM(S). SHOW THE LOCATIONS OF THE DEVICES ON THE
 LAYOUT PLAN AND INDICATE CONTROLS OPERATION AND THE
 MEANS OF SUPERVISION- SECTIONS 606.4 & 606.4.1.
 6) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE AC
 UNITS ON THE EXTERIOR WALL OF THE MODULAR STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  