2015-12-02 09:41:442302 PRESIDENTIAL WAY - CONSTRUCTION TRAILERS
 PERMIT #15110532
 REVIEW COMMENTS - FIRE DEPARTMENT
 STATUS ? FAILED BY FIRE DEPARTMENT. SUBMIT REVISION
 ADDRESSING PLAN REVIEW COMMENTS:
  
 **A #131 FIRE FINAL INSPECTION IS NEEDED BEFORE
 OCCUPANCY OF THE STRUCTURE IS PERMITTED**
  
 PROVIDE A PLAN SHOWING THE CONFIGURATIONS AND LOCATIONS
 OF THE TRAILERS IN CORRELATION TO OTHER STRUCTURES.
 SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES. PLEASE IDENTIFY AND SHOW
 CLOSET FIRE HYDRANT TO THE PROPOSED TRAILER.
  
 NO PLAN DETAILS SUBMITTED FOR STAIRS, HANDRAILS OR
 GUARDRAILS. HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE
 STAIR. HANDRAILS SHALL BE LOCATED NOT LESS THAN 34
 INCHES AND NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF
 THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE RAIL
 FROM THE LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL
 BE RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE
 PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS,
 MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR.
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE. STAIR RISERS SHALL
 BE BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS
 SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH
 OF 11 INCHES AND PREVENT THE ACCUMULATION OF WATER. NO
 PLATFORM / RAMP DETAILS ARE SHOWN FOR REAR EXIT / ENTRY
 DOUBLE DOORS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 NOTE: PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS;
 TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER. ALL TRAILERS GREATER THAN A
 ?DOUBLE WIDE? IN THE CITY OF WEST PALM BEACH IS
 REQUIRED TO BE SPRINKLED. PLEASE PROVIDE PLANS FOR A
 MONITORED SPRINKLER AS A SEPARATE/SUB PERMIT.
  
  