Date |
Text |
2015-12-02 09:41:44 | 2302 PRESIDENTIAL WAY - CONSTRUCTION TRAILERS |
| PERMIT #15110532 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| STATUS ? FAILED BY FIRE DEPARTMENT. SUBMIT REVISION |
| ADDRESSING PLAN REVIEW COMMENTS: |
| |
| **A #131 FIRE FINAL INSPECTION IS NEEDED BEFORE |
| OCCUPANCY OF THE STRUCTURE IS PERMITTED** |
| |
| PROVIDE A PLAN SHOWING THE CONFIGURATIONS AND LOCATIONS |
| OF THE TRAILERS IN CORRELATION TO OTHER STRUCTURES. |
| SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| ALL CONSTRUCTION ACTIVITIES. PLEASE IDENTIFY AND SHOW |
| CLOSET FIRE HYDRANT TO THE PROPOSED TRAILER. |
| |
| NO PLAN DETAILS SUBMITTED FOR STAIRS, HANDRAILS OR |
| GUARDRAILS. HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE |
| STAIR. HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 |
| INCHES AND NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF |
| THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE RAIL |
| FROM THE LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL |
| BE RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| 2 INCHES. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE |
| PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, |
| MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. |
| OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH |
| DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE |
| TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND |
| BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE |
| PASSAGE OF A 6-INCH DIAMETER SPHERE. STAIR RISERS SHALL |
| BE BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS |
| SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH |
| OF 11 INCHES AND PREVENT THE ACCUMULATION OF WATER. NO |
| PLATFORM / RAMP DETAILS ARE SHOWN FOR REAR EXIT / ENTRY |
| DOUBLE DOORS. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE |
| ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN |
| HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| BACKGROUND. |
| |
| STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| ADMINISTRATIVE CODE 69A-60.0081. |
| |
| NOTE: PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; |
| TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE |
| REQUIRED IN EACH TRAILER. ALL TRAILERS GREATER THAN A |
| ?DOUBLE WIDE? IN THE CITY OF WEST PALM BEACH IS |
| REQUIRED TO BE SPRINKLED. PLEASE PROVIDE PLANS FOR A |
| MONITORED SPRINKLER AS A SEPARATE/SUB PERMIT. |
| |
| |