2015-12-04 12:37:54 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE |
| LOCATION OF THE VARIOUS COMPONENTS OF THIS |
| INSTALLATION. |
| A) INDICATE ON PLAN THE PROPOSED ROUTE OF ALL FEEDERS; |
| WHETHER AERIAL OR UNDERGROUND. (ALL TRENCHING SHALL |
| REMAIN OPEN FOR INSPECTION. NO SITE TUBES WILL BE |
| ALLOWED) |
| B) INDICATE THE DISTANCE FOR EACH FEEDER FOR VOLTAGE |
| DROP CALCULATIONS. |
| 2. NEC 215.5 YOU SHALL PROVIDE A FEEDER DIAGRAM |
| INDICATING IN ADDITION TO THE ABOVE, THE LOAD CALCS AND |
| CONDUCTOR SIZING AND INSULATION. |
| 3. NEC 408.4 PROVIDE A CIRCUIT DIRECTORY AND MARK EVERY |
| PANELBOARD WITH THE LOCATION OF THE SOURCE DISCONNECT. |
| 4. NEC 110.16 ALL EQUIPMENT SHALL BE MARKED WITH THE |
| ARC-FLASH WARNING HAZARD LABEL. |
| 5. IN ADDITION TO THE ELECTRICAL SERVICE FOR THESE |
| UNITS, FBC SECTION 1006 REQUIRES THAT THE MEANS OF |
| EGRESS BY PROPERLY ILLUMINATED DURING THE TIME OF |
| OCCUPANCY. THE DRAWINGS DO NOT REFLECT ADEQUATE |
| ILLUMINATION. |
| 6. FBC FURTHER REQUIRES THAT THESE AREAS BE PROVIDED |
| WITH EMERGENCY LIGHTING. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |