2015-11-25 14:48:02 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15110532 |
| ADD: 2302 PRESIDENTIAL WAY |
| CONT: HEDRICK BROTHERS |
| TEL: 561-689-8880 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| 1ST REVIEW |
| DATE: WED. NOV. 25/ 2015 |
| ACTION: DENIED |
| |
| 1) PLEASE SUBMIT A SITE PLANS MISSING FROM THE 1ST |
| REVIEW. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| FOR BUILDINGS. 107.3.5.1.1 COMMERCIAL BUILDINGS (1.) |
| SITE PLAN REQUIREMENTS: |
| LOCATION OF JOBSITE. |
| PARKING |
| FIRE ACCESS |
| VEHICLE LOADING |
| DRIVING/TURNING RADIUS |
| FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) |
| SET BACK/SEPARATION (ASSUMED PROPERTY LINES) |
| LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES |
| FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| ELEVATIONS |
| |
| 2) THE MOD SPACE PLANS DO NOT HAVE A DCA STATE APPROVAL |
| BY A 3RD PARTY AGENCY. THE PLANS ARE THE EQUIVALENT TO |
| A SITE BUILT STRUCTURE. CAN INSPECTION AFFADAVITS FROM |
| THE MANUFACTURER PLANT BE OBTAINED, IF NOT THE |
| STRUCTURE HAS TO BE OPENED UP FOR THE CITY STAFF TO BE |
| ABLE TO VERIFY CODE COMPLIANCE. |
| |
| 3) THIS STRUCTURE IS GOING TO BE USED AS TEMPORARY GOLF |
| FACILITY. THE TERM TEMPORARY IS LESS THAN 180 DAYS. THE |
| USE WILL REQUIRE COMPLIANCE WITH EITHER LARGE MISSILE |
| IMPACT WINDOWS OR STORM SHUTTERS FOR ALL GLAZED |
| OPENINGS. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (E) SHUTTERS |
| |
| 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 5) STORM SHUTTERS. PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC |
| ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT |
| GLAZING. FBC 1609.1.2. |
| FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 A |
| COMPLETE INSTALLATION SCHEDULE SUMMARIZING & |
| IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR. |
| |
| 6) DESIGN DOCUMENTS BY RANDELL STOIFT ARCHITECT FOR |
| ACCESSIBLE STAIRS, RAMP AND LANDING: |
| |
| 6A) SHEET A001 DESIGN PARAMETERS INDICATE BUILDING |
| CLASSIFICATION AS A R-3 OCCUPANCY, BUT THE PLANS STATE |
| TEMPORARY GOFL FACILITY. PLEASE CORRECT OCCUPANCY |
| PROUP. 2010 FBC-B 304.1. |
| |
| 6B) NO WIND DESIGN WAS PROVIDED ON ANY OF THE PLANS. |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| |
| 6C) SHEET A101 & A102 ARE DETAIL SHEETS THA ARE |
| INCOMPLETE. THERE ARE MANY IDENTIFICATION TAGS, BUT NO |
| LEGEND AS TO WHAT THEY ARE. THERE ARE NO HEIGHT |
| DIMENSIONS FOR HANDRAILS NOR GUARDRAILS. THE PLANS ARE |
| BASICALLY INCOMPLETE IN FOR THE SCOPE OF WORK OUTLINED. |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| |
| 6D) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| CORRECT A CODE VIOLATION. |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| |
| |