Plan Review Notes
Plan Review Notes For Permit 15110524
Permit Number 15110524
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-13 17:03:241ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
 JOB PERMIT NUMBER: 15110524
 JOB ADDRESS: CHARLESTOWN COMMONS VILLAS
 5025 ERNEST ST WEST PALM BEACH
 DATE: JAN 13 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. IN REGARDS WITH UNIT A , B ,C THE OCPD RATING FOR
 THE WATER HEATER IS UNDERSIZED THE E3 FBC-R E4101.4.1
 SINGLE NON-MOTORED OPERATED APPLIANCE STATES THE
 FOLLOWING (3) NOT EXCEED 150 PERCENT OF THE APPLIANCE
 RATED CURRENT IF THE OVERCURRENT PROTECTION RATING IS
 NOT MARKED (?) AND THE APPLIANCE IS RATED OVER 13.3
 AMPERES. WHERE 150 PERCENT OF THE APPLIANCE RATING DOES
 NOT CORRESPOND TO A STANDARD OVERCURRENT DEVICE AMPERE
 RATING, THE NEXT HIGHER STANDARD RATING SHALL BE
 PERMITTED.
 2. TW-ROMEX IS A TECHNICALLY A BRAND NAME NOT A WIRING
 METHOD YOU MIGHT WANT TO REFERENCE TYPE NM , NMC, AND
 NMS IN YOUR PANEL SCHEDULE UNDER CONDUCTORS.
 3. PANELS SEEMED TO BE LOCATED IN A DARK AREA WERE
 SERVICING MIGHT REQUIRE ILLUMINATION FBC-R E3405.6
 4. PLEASE ADD TO NOTES R402.4.4 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN
 AIR LEAKAGE RATE NOT MORE THAN 2.0 CFM (0.944 L/S) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF (75
 PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES
 SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE
 HOUSING AND THE INTERIOR WALL OR CEILING COVERING.
 5.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
  