2016-01-13 17:03:24 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6700 |
| [email protected] |
| ALTERNATE CONTACT |
| MIKE ALBARRAN |
| 561-805-6746 |
| [email protected] |
| JOB PERMIT NUMBER: 15110524 |
| JOB ADDRESS: CHARLESTOWN COMMONS VILLAS |
| 5025 ERNEST ST WEST PALM BEACH |
| DATE: JAN 13 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| 1. IN REGARDS WITH UNIT A , B ,C THE OCPD RATING FOR |
| THE WATER HEATER IS UNDERSIZED THE E3 FBC-R E4101.4.1 |
| SINGLE NON-MOTORED OPERATED APPLIANCE STATES THE |
| FOLLOWING (3) NOT EXCEED 150 PERCENT OF THE APPLIANCE |
| RATED CURRENT IF THE OVERCURRENT PROTECTION RATING IS |
| NOT MARKED (?) AND THE APPLIANCE IS RATED OVER 13.3 |
| AMPERES. WHERE 150 PERCENT OF THE APPLIANCE RATING DOES |
| NOT CORRESPOND TO A STANDARD OVERCURRENT DEVICE AMPERE |
| RATING, THE NEXT HIGHER STANDARD RATING SHALL BE |
| PERMITTED. |
| 2. TW-ROMEX IS A TECHNICALLY A BRAND NAME NOT A WIRING |
| METHOD YOU MIGHT WANT TO REFERENCE TYPE NM , NMC, AND |
| NMS IN YOUR PANEL SCHEDULE UNDER CONDUCTORS. |
| 3. PANELS SEEMED TO BE LOCATED IN A DARK AREA WERE |
| SERVICING MIGHT REQUIRE ILLUMINATION FBC-R E3405.6 |
| 4. PLEASE ADD TO NOTES R402.4.4 RECESSED LIGHTING. |
| RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED |
| LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN |
| AIR LEAKAGE RATE NOT MORE THAN 2.0 CFM (0.944 L/S) WHEN |
| TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF (75 |
| PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES |
| SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE |
| HOUSING AND THE INTERIOR WALL OR CEILING COVERING. |
| 5. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| |