Plan Review Notes
Plan Review Notes For Permit 15110524
Permit Number 15110524
Review Stop B
Sequence Number 1
Notes
Date Text
2016-01-14 11:35:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW: (ALSO SEE MARK
 UPS ON DIGITAL PLANS FOR PERMIT #15110523.)
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION. CHECK CODE SECTIONS AND THE EDITION OF
 THE CODE THAT IS CITED IN THE PLANS. I CLOUDED MOST OF
 THEM IN RED ON THE PLANS.
  
 2) THE EMERGENCY MEANS OF ESCAPE NOTE AT THE ENTRY DOOR
 IS INCORRECT. THE DOOR IS REQUIRED TO BE IMPACT
 RESISTANT AND IMPACT PROTECTION DEVICES CAN NOT BE USED
 PER FBCR 310.4.
  
 3) THE CODE SECTION FOR UNDER STAIR PROTECTION IS
 R302.7 IN THE 2014 FBCR AND NOT R311.2.2
  
 4) THE ROOF COVERING NOTES ON C2 AND C3 REFERENCE THE
 2010 FBC.
  
 5) THE GENERAL NOTES TYPICAL TO UNITS A, B AND C
 REFERENCE THE 2010 FBC AND WRONG CODE SECTIONS IN
 SEVERAL PLACES.
  
 6) THE FLAME SPRED AND SMOKE DEVELOPED NOTE #19 IS
 INCORRECT. INSULATION MATERIALS SHALL HAVE A FLAME
 SPRED INDEX NOT TO EXCEED 25 PER FBCR 302.10.1. SEE FBC
 R302.9.1 AND R302.9.2 FOR FLAME SPREAD AND SMOKE
 DEVELOPED REQUIREMENTS FOR WALL AND CEILING FINISHES.
  
 7) THERE IS A DETAIL FOR A SHADOW BOX WOOD FENCE (WING
 WALL) IN THE DOCUMENTS THAT NEEDS TO BE REMOVED. A
 SEPARATE PERMIT, APPLICATION AND DRAWINGS ARE REQUIRED
 FOR FENCES. THE DETAIL DOES NOT SPECIFY THE HEIGHT AND
 DOES NOT PROVIDE AND STRUCTURAL DETAILS. FBC 107.2.1
  
 8) THE -50 PSF DESIGN PRESSURE IN PRODUCT APPROVAL
 FL15037.3 FOR THE ENTRY DOOR IS NOT ADEQUATE. THE PLANS
 SPECIFY A REQUIRED NEGATIVE PRESSURE OF -55.08 PSF FOR
 THE DOOR. FBC R301.1
  
 9) THE ANCHOR SPACING COLUMN ON THE STORM PANEL
 INSTALLATION SCHEDULE FOR 1441-A END UNIT IS BLANK. THE
 ANCHOR SPACINGS ARE MISSING. FBC 107.2.1
  
 10) THE STORM PANEL INSTALLATION SCHEDULES FOR END
 UNITS A AND B ARE MISSING THE WINDOWS ON THE ENDS. FBC
 107.2.1
  
 11) SUBMIT TWO COPIES OF A KEY PLAN THAT CORRESPONDS
 WITH THE STORM PANEL INSTALLATION SCHEDULE TO SHOW THE
 LOCATIONS OF THE OPENINGS. FBC 107.2.1
  
 12) SOME OF THE PLAN SHEETS AND DOCUMENTS ARE NOT
 SIGNED AND SEALED. VERIFY THAT ALL REQUIRED SUBMITTALS
 ARE SIGNED AND SEALED. FS 471 AND 481
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  