Plan Review Notes For Permit 15110501 |
Permit Number |
15110501 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-01-05 10:00:19 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | SECT. 103.1.1.2 CODE COMPLIANCE CERTIFICATION. | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION. | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SUBMIT TWO COPIES OF FL OR NOA | | NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM | | DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING | | MATERIALS THAT ARE SPECIFIED ON THE PLANS. (BUR AND | | CONCRETE BARREL TILE) NOTE: THE PRODUCT APPROVALS FOR | | ROOF COVERING MATERIAL FOR FLAT ROOF TYPICALLY HAVE THE | | FASTENER SPACING AND DESIGN PRESSURES FOR ROOF ZONE 1 | | AND REQUIRE RAS 117 CALULATIONS FOR ROOF ZONES 2 AND 3. | | | | | | | | | | | | |
|