2015-12-09 08:35:31 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY MECHANICAL |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION |
| SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER |
| CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS |
| 402 OR 405. |
| FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE |
| COMPLIANCE CERTIFICATION. |
| THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION. |
| |
| 2) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL |
| PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS |
| PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. FBC |
| -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW CRITERIA: |
| SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, KITCHEN |
| EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, |
| EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, |
| ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, |
| COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, |
| APPLIANCES, BOILERS, REFRIGERATION, BATHROOM |
| VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. |
| |
| 3) FBC-R - M1401.3 SIZING. HEATING AND COOLING |
| EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS |
| CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| PROVIDE EQUIPMENT SIZING CALCULATIONS. |
| |
| |
| |
| |