2015-11-17 07:44:42 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15110492 |
| 11/17/15 |
| |
| 1) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| SPRAY BOOTH AND SPRAY EQUIPMENT REVIEWED AND STAMPED BY |
| THE ENGINEER OF RECORD- REFERENCE NFPA 33 SECTIONS |
| (5.1.1), )5.1.4), (7.10.1), (8.3.2), (11.1), (12.1). |
| 2) THE LOCATIONS OF THE SPRAY BOOTH SHOWN ABUTTING THE |
| EXTERIOR CONCRETE WALL AT THE EAST SIDE DOES NOT LEAVE |
| AMPLE SPACE FOR MAINTENANCE AS REQUIRED BY SECTION |
| 5.3.2 EXCEPTION (2) NFPA 33. |
| 3) A 4X4' LOUVER IS SHOWN IN THE PLAN FOR MAKE-UP AIR. |
| PLEASE PROVIDE AN EXHAUST VENTILATION CALCULATION USING |
| THE PERCENTAGE OF FREE AIR AVAILABLE THROUGH THE |
| LOUVERED OPENING- SECTION 502.7.3.1 FBC-14 MECHANICAL. |
| 4) PROVIDE AN AIR VELOCITY CALCULATION FOR THE SPRAY |
| BOOTH IN COMPLIANCE WITH SECTION 502.7.3.3 FBC-14 |
| MECHANICAL. |
| 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND A FL. |
| PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE LOUVER |
| REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. THE |
| LOCATION OF THE LOUVERED OPENING SHALL BE IN COMPLIANCE |
| WITH SECTION 401.4, AND BE PROTECTED FROM WEATHER IN |
| ACCORDANCE WITH SECTION 401.5. |
| 6) INDICATE HOW THE EXHAUST DUCT IS BEING SUPPORTED IN |
| THE AREA BETWEEN THE TOP OF THE BOOTH AND THE ROOF |
| LEVEL- SECTION 7.8 NFPA 33. |
| 7) REFERENCE SECTION 501.3.1(1) FBC-14 MECHANICAL AND |
| PROVIDE A PLAN VIEW OF THE ROOF AND SITE THAT SHOWS THE |
| REQUIRED MINIMUM CLEARANCE DISTANCES FOR THE SPRAY |
| BOOTH EXHAUST TERMINATION TO PROPERTY LINES, AIR |
| INTAKES, COMBUSTIBLE CONSTRUCTION, EXTERIOR WALLS, AND |
| OPERABLE OPENINGS. |
| 8) INDICATE THE TYPE AND SIZE OF COMPRESSED AIR PIPING |
| TO BE INSTALLED AND HOW IT WILL BE SUPPORTED- INDICATE |
| THE TYPE AND SPACING OF THE HANGERS. |
| 9) PROVIDE A THROUGH PENETRATION FIRE STOPPING METHOD |
| FOR THE COMPRESSED AIR PIPING PENETRATING THE BOOTH. |
| 10) PROVIDE FIRE SUPPRESSION PLANS- SECTION 9.1 NFPA |
| 33. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |