Plan Review Notes
Plan Review Notes For Permit 15110492
Permit Number 15110492
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-17 14:10:35BUILDING PLAN REVIEW
 W. P. B. PERMIT:15110492
 ADD: 6212 GEORGIA AVE.
 CONT: FLORIDA FILTRATION
 TEL: (561)582-5543
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2014
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 17/ 2015
 ACTION: DENIED
  
 1) THERE IS A DISCREPANCY IN THE PLAN.SHEET B1. THE
 PLANS SHOW THE FLOOR LAYOUT OF 2 SPRAY BOOTHS, ONE WITH
 A MIXING ROOM & SPRAY BOOTH THE OTHER DETAIL SHOWING A
 SINGLE SPRAY BOOTH. PLEASE REPRESENT THE ACTUAL LAYOUT
 NOT A GENERIC SHEET THAT COVERS ALL INSTALLATIONS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 2) SHEET A-2 SHOWS AN OVER HEAD VIEW AND ELEVATIONS OF
 THE SPRAY BOOTH. THIS REVIEW THERE HAVE BEEN NO
 SUBMITTALS MANUFACTURERS SPECIFICATIONS, DETAILS OF
 COMPLIANCE WITH SECTION 416.4 SPRAY BOOTHS SHALL BE
 DESIGNED, CONSTRUCTED AND OPERATED IN ACCORDANCE WITH
 THE FIRE PREVENTION CODE, NFPA 33. THE DESIGNER OF
 RECORD IS TO REVIEW ALL SUBMITTALS, SHOP DRAWING, ETC
 BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. ADDITIONAL
 COMMENTS MAY FOLLOW ONCE SHOP DRAWINGS ARE SUBMITTED.
  
 3) SHEET B-1 SHOWS A 48" X48" WALL LOVER THROUGH THE
 WALL. NOTE PLANS DO NOT INDICATE HOW THE HOLE IN THE
 WALL WILL BE RE-INFORCED? BLOCK WALL, LINTEL, NEW
 VERTICAL REBARS TO BE PART OF THE MWFRS (MAIN WINF
 FORCE RESISTING SYSTEM). WALL TYPE IS NOT IDENTIFIED?
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (C) WALL LOUVERS
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) SHEET B-2 SHOWS SHOWS A SIDE ELEVATION WITH THE
 EXHAUST DUCT PENETRATING THE ROOF DECK. THE PLANS DO
 NOT INDICATE THE WHAT THE STRUCTURAL DECK AND FRAMING
 MEMBERS IS MADE OF. NO FRAMING OR INFILE FRAMING IS
 PROVIDED AROUND THE NEW ROOF DECK PENETRATION? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 7) THE PLANS DO NOT SHOW HOW COMPLIANCE WITH 2014 FBC-B
 416.5 FIRE PROTECTION. AN AUTOMATIC SPRINKLER SYSTEM OR
 FIRE -EXTINGUISHING SYSTEM SHALL BE PROVIDED IN ALL
 SPRAY BOOTHS AND INSTALLED IN ACCORDANCE WITH FBC-B
 CHAPTER 9.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  