2015-11-16 08:51:38PERMIT # 15110474
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EVENT PLAN IS APPROVED WITH THE COMMENTS:
  
 1) A SEPERATE PERMIT IS REQUIRED FOR THE INSTALLATION
 AND USE OF A TENT. THE TENT COMPANY PROVIDING THE TENT
 MUST APPLY FOR THE TENT PERMIT PRIOR TO THE EVENT DATE
 OR 4 TIMES THE PERMIT FEE SHALL BE IMPOSED.
  
 2)PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 3) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 4) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 5) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 6) PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE
 CANOPY MATERIAL.
  
 7) IF USED, GENERATORS AND OTHER INTERNAL COMBUSTION
 POWER SOURCES SHALL BE SEPARATED FROM TENTS BY A
 MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM CONTACT
 BY FENCING OR ENCLOSURE
  
  