2015-11-19 14:40:041ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110453
 11/19/15
  
 1) REFER TO SECTION 809.2 FBC EXISTING BUILDING CODE:
 809.2 ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62. PROVIDE MINIMUM VENTILATION
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.3 FBC-14
 MECHANICAL.
 2) SHEET M2.1: A) PLEASE PROVIDE KEY NOTES TO CLARIFY
 THE SCOPE OF WORK SHOWN IN THE DRAWING. B) PROVIDE AN
 EQUIPMENT SCHEDULE FOR THE VAV BOXES, AND CLARIFY THE
 PRINT SHOWN ON THE BOXES- IT IS ILLEGIBLE. C) PROVIDE
 THE FLEX DUCT SIZES. D) PROVIDE AN AIR DEVICE SCHEDULE.
 3) M2.1: THE PLAN SHOWS RETURN AIR BEING TRANSFERRED
 FROM THE ROOMS TO THE CORRIDOR- SEE SECTION 601.2: AIR
 MOVEMENT IN EGRESS ELEMENTS. CORRIDORS SHALL NOT SERVE
 AS SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION AIR
 DUCTS. PLEASE CORRECT THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER