2015-11-20 15:36:361ST REVIEW 2014 MECHANICAL
 PERMIT #15110375
 11/20/15
  
 1) THE MECHANICAL REVIEW IN ENTIRETY IS RESERVED
 PENDING RESPONSES TO FIRE AND BUILDING PLAN REVIEWS
 COMMENTS REGARDING FIRE-RATED WALLS AND PARTITIONS.
 PLEASE NOTE THAT FIRE DAMPERS MAY BE REQUIRED FOR AC
 DUCTS PENETRATING THESE WALLS AND PARTITIONS, ALONG
 WITH OTHER CODE COMPLIANCES.
 2) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC-2 MINI-SPLIT SYSTEM IN THE STORAGE ROOM- SEE
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
 3) PROVIDE ENERGY CALCULATIONS- REFER TO SECTION C101.2
 FBC-14 ENERGY CONSERVATION
 4) M1-1: PROVIDE WIND LOAD ENGINEERING AND DESIGN
 CRITERIA FOR INSTALLATION OF THE NEW CONDENSER AND
 EXHAUST FAN ON THE ROOF- SECTION 301.15 FBC-14
 MECHANICAL
 5) M1-1 & M1-3: EF-2 IS INDICATED AS SERVICING THE
 WAREHOUSE IN THE EQUIPMENT SCHEDULE BUT APPEARS TO BE
 OVER THE LAB IN THE ROOF DRAWING: PLEASE CLARIFY OR
 CORRECT.
 6) M1-1 & M1-2: SHOW THE LOCATIONS OF KEY NOTES 6, 8, &
 16.
  