Plan Review Notes For Permit 15110375 |
Permit Number |
15110375 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-07 13:19:28 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6700 | | [email protected] | | ALTERNATE CONTACT | | PHIL PETTY | | 561-805-6742 | | [email protected] | | | | | | THE ELECTRICAL REVIEW IN ENTIRETY IS RESERVED PENDING | | RESPONSES TO FIRE , BUILDING , AND MECHANICAL REVIEW | | COMMENTS REGARDING FIRE PENETRATIONS ON WALLS AND | | PARTITION. | | PLAN E 1 SHOWS 400 AMP PANEL AS EXISTING AND I BELIEVE | | ITS NEW ACCORDING TO THE SCOPE OF WORK. | | PLAN E 3 PLEASE SHOW EMERGENCY LIGHTING IN STAIRS FBC | | 1006 NEC 700.16 | | FBC 1006.1 MEANS OF EGRESS ILLUMINATION. | | FBC 1006.1.1 PER FBC-R, T-E3403 | | ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN | | ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND | | STRUCTURE. | | 700.16 EMERGENCY ILLUMINATION. EMERGENCY ILLUMINATION | | SHALL INCLUDE ALL REQUIRED MEANS OF EGRESS LIGHTING, | | ILLUMINATED | | EXIT SIGNS, AND ALL OTHER LIGHTS SPECIFIED AS NECESSARY | | TO PROVIDE REQUIRED ILLUMINATION. | | PROVIDE MANUFACTURE SPECS ON AC EQUIPMENT. | | | | | | | | |
|