2016-02-22 17:40:10 | 2ND ELECTRICAL REVIEW NOTES FOR PERMIT #: 15110245, |
| 15110318, 15110330, 15110346, 15110351, 15110356 & |
| 15110362 |
| REVIEWED FOR COMPLIANCE WITH: FBC 5TH EDITION 2014 & |
| NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| SHEET A-E 1 COMMENT #9: I MENTIONED THE NEED FOR A |
| SECOND WALL SWITCH FOR THE LOCATIONS WHERE YOU INTEND |
| TO HANG A PADDLE FAN. YOUR RESPONSE ONLY CONFIRMS THAT |
| THERE WILL BE A PADDLE FAN W/A LIGHT KIT. NEC |
| 210.70(A)(1) MANDATES THAT BE AT LEAST ONE WALL SWITCH |
| CONTROLLED LUMINAIRE IN EVERY HABITABLE ROOM, THEREFORE |
| IF YOU WILL NOT BE ADDING THE SECOND SWITCH, YOU SHALL |
| MAKE SURE THAT THE SWITCH CONTROLS THE LUMINAIRE AND |
| NOT THE FAN. |
| |
| SHEET B-E 1 COMMENT #10: SAME AS ABOVE. |
| |
| SHEET C-E 1 DIDN?T HAVE THE ABOVE COMMENT MENTIONED BUT |
| THE REQUIREMENT APPLIES AS WELL. |
| |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |